Installation and Circuitry
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
197
DC8-037-2.02, Edition 10.2017
6.7.3 Process
Peripherals
Cabinet-internal wiring is preferably carried out with plastic-insulated cables according to
DIN VDE 298 T4 2/89. Use only copper wires.
You can establish the connections with single leads of the type H05V-K or H05V2-K
(0.5…1 mm²), as well as H07V-K or H07V2-K (1.5…2.5 mm²).
Max. ambient temp.
Max. operating temp.
Type
55°C
70°C
H05V-K, H07V-K
70°C
85°C
H05V2-K, H07V2-K
•
If a wire bridge with 0.75 mm² is used or a bridged comb, the cable cross section is limited
to 1.5 mm².
•
The construction of the peripheral connectors is designed for direct peripheral wiring. That
means, that the wiring can be carried out without the use of a routing terminal or other ad-
ditional screw terminals.
•
Removable screw terminals are used as peripheral connectors. These are attached to the
device for delivery. Optionally spring-loaded- or crimp terminals can be used.
•
Preferably wire end sleeves are to be used.
•
A cable duct is to be provided for the wiring of the process signals.
6.7.4 Shielding
CP-8000/CP-802
x
is designed in order that no shielded cables are necessary.
Normally, shielded cables are strain-relieved directly after the cabinet/rack entry and then
grounded on a large-surface screening rail installed for this purpose. The device itself pro-
vides no possibility of shield clamping.
6.7.5 Protective
Earth/Ground
When installing CP-8000/CP-802
x
, it is to be ensured that the cabinet or rack used has proper
protective earth and ground. That means, that all electrical conducting parts must be
connected large-surface and as short as possible with the existing grounding system.
If these preconditions exist, the grounding of the device takes place via the connection of the
DIN rail with the cabinet spar. A reliable connection is achieved by using screws with contact
washers.
Содержание CP-8000
Страница 10: ...Open Source Software 10 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 74: ...Function Packages 74 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 468: ...Engineering via SICAM WEB 468 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 524: ...Service 524 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 556: ...Error Handling 556 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 603: ...Use Cases SICAM A8000 CP 8000 CP 8021 CP 8022 Manual Unrestricted 603 DC8 037 2 02 Edition 10 2017 ...
Страница 604: ......