Requirements for Use
B3–7
CP 443-5 Basic for PROFIBUS / Manual Part B3 –
Release 11/2002
C79000-G8976-C161-03
Requirements for Use
The CP 443-5 Basic described here is supported by all the CPU operating systems
listed in the table below.
The chapter also contains the following information:
S
The number of CPs that can be operated with one CPU.
S
The number of AG-SEND or AG-RECV calls on the SEND/RECEIVE interface
that can be active at the same time (data exchange on FDL connections over
PROFIBUS and corresponding connections over Industrial Ethernet).
2.1
Use with the Current CPU Types
When operating the CP 443-5 Basic with the CPU types listed here in the table,
the following functionality is supported without exception:
S
Number of operable CPs: 14
S
Multicomputing (except for H systems)
Table 2-1
Use with the Current CPU Types
CPU
Order number
Firmware version
Number of AG-SEND or AG-RECV
calls at same time
CPU 412
6ES7 412-1XF03-0AB0
As of V3.0
24 / 24
CPU 412-2
6ES7 412-2XG00-0AB0
As of V3.0
CPU414-2 128 KB
6ES7 414-2XG03-0AB0
As of V3.0
CPU414-3 384 KB
6ES7 414-3XJ00-0AB0
As of V3.0
CPU 414-4H
6ES7 414-4HJ00-0AB0
As of V3.0
CPU416-2 0.8 MB
6ES7 416-2XK02-0AB0
As of V3.0
64 / 64
CPU416-3 1.6 MB
6ES7 416-3XL00-0AB0
As of V3.0
CPU 417-4
6ES7 417-4XL00-0AB0
As of V3.0
CPU 417-4H
6ES7 417-4HL00-0AB0
As of V2.1
6ES7 417-4HL01-0AB0
As of V3.0
CPU416F-2 1.6 MB
6ES7 416-2FK02-0AB0
As of V3.1
64 / 64