background image

Installation Sheet

November, 2016

Supersedes January 2016

s

E87010-A0105-T003-A6-CLM0

Lighting and Heating Contactor 

60, 100, 200 Amp 

2, 3, 4, 5 Pole 

Magnetically Latched

A5E31166448A-006

Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092 

    

Contactor Rating

Catalog Number

CLM0D...  CLM0E...  CLM0F...

Cont. Current Rating, Amp.

200

100

60

Tungsten

Max. Volts, line-line

480

480

480

Max. Volts, line-Neutral

277

480

277

480

480

277

Ballast

Max. Volts, line-line

Max. Volts, line-Neutral

346

600

600

600

346

600

600

Heating

Max. Volts, line-line

600

600

600

Max. Volts, line-Neutral

346

30

480

277

600

346

600

346

30

480

277

600

346

600

30

480

277

600

346

600

346

600

600

600

600

346

Table 1

Theory of Operation

Each contactor contains a permanent magnet built into its struc-

ture that will maintain the contactor in its energized state indefi

-

nitely without using control power. When energized, DC voltage 

is applied to produce a magnetic field that reinforces the polarity 

of the permanent magnet and the contactor closes. Immediately, 

the current to the coil is disconnected by the coil clearing aux-

iliary contact. In order to open the contactor, it is necessary to 

create a field through the OFF coil in the reverse direction to the 

permanent magnet. This momentarily cancels the magnetic at-

traction and the contactor drops out.

Each CLM contactor has an electronic control module 

“CLMKCMR” which is used to energize and close the contactor 

and for the release circuit. It is designed for short time actuation 

of 1-3 cycles only. All coils are designed with a small wattage 

resistor in addition to a diode at coil voltages higher than 120 

volts. 

Remote  solid  state  switching  devices  have  ‘off  state’ 

leakage currents. They may also pass utility transient voltages 

through to the device electronics. 

Magnetically latched CLM lighting and heating contactors can 

control tungsten, fluorescent and metal vapor lamp or heating 

loads. (Table 1 below shows the voltage and current rating for 

various loads). Each contactor and its associated load should be 

protected against short circuits by a suitable branch circuit pro-

tective device selected in accordance with the National Electric 

Code (NEC).

Description

  

The low level ‘off state’ voltages are insufficient to actuate 

the contactor but large enough to burn out the resistors. 

Normal  actuating  voltages  are  quickly  disconnected  from 

the coils and control module by the latch clearing contacts. 

Coil and module failures are possible when used 

with solid 

state relays and PLC outputs. 24-volt systems are ok to use, 

but  120  volts  and  above  should  be  discouraged.  If  higher 

voltages cannot be avoided, an interposing relay should be 

used. 

Care should be taken when servicing that leads do not be-

come changed from their factory installed terminals, or im

-

proper operation and possibly permanent damage to the 

contactor could result.

Table 1 -

 This industrial type contactor is designed to be installed, operated, and 

maintained by adequately trained personnel. These instructions do not cover all 

the variations of all of the topics covered herein. Contact your local sales office if 

you have questions regarding the product.

CAUTION - 

Device sensitive to current polarity.

Risk of damage to this device.

Do not apply AC voltage directly to the coil terminals of this device! 

The permanent magnet will be demagnetized and the rectifier will be 

damaged if alternating current or wrong polarity direct current is applied 

directly to the coil.

CAUTION - 

High inrush.

Can cause damage to this device.

Avoid attempting to manually latch or delatch the contactor.

 

Содержание CLM0D Series

Страница 1: ...e leakage currents They may also pass utility transient voltages through to the device electronics Magnetically latched CLM lighting and heating contactors can control tungsten fluorescent and metal vapor lamp or heating loads Table 1 below shows the voltage and current rating for various loads Each contactor and its associated load should be protected against short circuits by a suitable branch c...

Страница 2: ...0 45 50 10 Main Power Connector 2 pole 13 Cover Screw 2 100 and 200 Ampere Contactors Coil Wire Connector 2 8 9 12 Stationary Contact Screw 2 pole 10 90 100 13 275 300 13 Main Power Connector 2 pole 100 Amp Main Power Connector 2 pole 200 Amp 18 18 20 18 20 Installation The nameplate ratings of the contactor must agree with the power supply and the rating of the load Contactor mounting should be s...

Страница 3: ... both mechanical and electrical wear during their operation In most cases mechanical wear is insignificant The erosion of the contacts is due to electrical wear During arcing material from each contact is vaporized and blown away from the useful contacting surface Note When contact replacement is required it is necessary to replace both stationary and moving contacts plus moving contact overtravel...

Страница 4: ... ON OFF Red CR Remote Device CR CR CLM CONTACTOR ON OFF ON OFF Black AC AC L2 Red White CLMFCCK11 3 2 CLMFCAK11 OFF ON Red Pushbutton Momentary ON OFF Pushbutton Maintained 1 L1 L3 L2 T1 T3 T2 Red Lead A Not Provided CLM CONTACTOR VOLTAGE CONTROL ON OFF BLACK AC AC L2 RED WHITE CLMFCCK11 3 2 RED ON OFF RED CR REMOTE CR CR L1 1 L2 X2 H A O DEVICE SELECTOR SWITCH CLM CONTACTOR Fig 5 Connection for H...

Страница 5: ...nd 200 Amp Device CAUTION Coil must be wired correctly Risk of damage to the device All control wiring for contactor operation must only be made to the coil isolation contact terminals 2 3 and L2 terminal con nection points Wiring made to any other terminal points will burn out the coil and diode If a coil burnout occurs both the coil and the diode must be replaced Table 6 AC Operating Coils for 6...

Страница 6: ... Volts Remote solid state switching devices have off state leakage currents They may also pass utility transient voltages through to the device electronics The low level off state voltages are insufficient to actuate the contactor but large enough to burn out the resistors Normal actuating voltages are quickly disconnected from the coils and control module by the latch clearing contacts Coil and m...

Отзывы: