Siemens Class 87 Скачать руководство пользователя страница 2

E87010-A0095-T003-A4-87DU 

Siemens Industry, Inc. 3617 Parkway Ln., Peachtree Corners, GA 30092     

Installation (Figure 1)
1. Remove the enclosure cover from the case.
2. Remove the knockout in the cover.
3. Mount pilot device support bracket assembly with two  
  mounting screws in location 

A (Size 1) or B (Size 2 and 3), 

  tighten screws to 25 lb.-in.
4. For pushbutton 3-wire control, make electrical connections
  per Figure 2.
5. For the 2 and 3 position selector switches, make electrical    
  connections as shown in Figures 3, 4, 5, and 6.
6. Location of auxiliary interlocks may differ from diagrams,  

 

  therefore, markings on units should be followed.
7. Affix the appropriate legend label onto the cover next to the   
  pilot device.

Important! Prior to performing steps 1 through 13 verify that  
all power is turned off to the pump control panel.
1.  Examine each device on the panel for shipping damage and if  
 

any is noted, notify carrier for claim. Do not apply power to  

 

any damaged device.

2.  Operate disconnect switch or circuit breaker with external  
 

handle to verify operation.

3.  Manually operate magnetic starter contactor to determine that 
 

moving parts do not bind. Manual operation of the contactor  

 

is performed by pressing on the movable contact assembly as  

 

shown in Figure 1 for Class 87 and Figure 2 for 3RE48. 

4.   Verify that the supply voltage matches the voltage rating of the  
 

pump panel.

5.  Verify that the horsepower rating of the motor does not exceed  
 

the horsepower rating of the pump control panel and the current  

 

rating of the motor is within the adjustable range of the overload  

 

relay. Set the FLA dial on the overload relay to the motor FLA.  

 

Make sure the DIP switches are set to trip class 10 for pumping  

 

applications. Refer to the overload elay instruction sheet 

 

for details.

6.   Install in conformance with National Electric Code – NFPA70 
 

 in the US or Canadian Electrical Code – CSA C22.1 in Canada, 

 

 and any applicable local electric codes. 

7.  Install the proper size dual element fuses in the disconnect  
 

switch. The disconnect switch and fuse load block will accept  

 

Class H, K, J or R fuses depending on the fuse holder. If the  

 

available fault current of the supply is greater than 10kA, Class  

 

R or J fuses must be used. Verify the available fault current of  

 

supply does not exceed the interrupting rating of the fuses in   

 

stalled and does not exceed the short circuit rating of the  

 

pump panel controller. 

8.  If the pump controller includes an instantaneous trip breaker,  
 

adjust the trip setting of the breaker according to the instruction  

 

on the door label. Verify the available fault current of the  

 

supply does not exceed the short circuit current rating of the    

 

pump controller.

9.  Firmly fasten enclosure to solid mounting surface with customer  
 

supplied fasteners.

10. Install necessary grounding means and wire pump control panel  
 

in accordance with wiring diagram supplied. Conduits installed  

 

in knockouts at the bottom of the enclosure must be located    

 

below all live parts. Conduit hubs or fittings installed on the top  

 

or side walls of the enclosure must have a NEMA 3R rating.  

Press Movable  
Contact Assembly  
here

Press Movable  
Contact Assembly  
here

Figure 1

Figure 2

11. Check that all wiring is secure and does not interfere with  

 

 

proper operation of any devices.

12. Check that all wiring connections are tight, including  
 

factory connections.

13. Make a final installation check of steps 1 through 12 and  

 

 

remove any foreign material from the enclosure.

A5E31166437A-004

Installation of Class 87 and 3RE48 Pump Panels

 

Hazardous voltage.

Can cause death, serious personal injury, or  

property damage. 
Disconnect power before working on this equipment.

WARNING