Programming
PXL Conventional Fire Alarm Control Panel
49
A
A
A
=
=
=
B
B
B
C
C
TIME
Time at which the System initially recognizes an alarm
from a smoke detector.
Retard/Reset Time
The time during which the System ignores the alarm
data. System default is 15 seconds plus 6 seconds for
PXL delay.
The 60 seconds during which the System alarms if the
device is returning alarm data.
Figure 24
Line Graph of Alarm Verification
Generic Zone
The Generic zone is activated (or alarmed) by the output from an-
other control panel. This output should be made with a contact
device connected across the Generic zone. When activated, it
causes the notification appliance circuits to sound and the appropri-
ate initiating Zone LED to light. When the input is deactivated, the
NACs will silence regardless of any inhibit timer. The System alarm
contacts
do not
change state. Do not map Generic zones to non-
silenceable bell circuits.
Reset Zone
The Reset zone is activated by a contact device such as the Space
Age Electronics Model DM4 shorting the zone. A momentary contact
closure will cause the PXL System to reset.