6
Siemens Building Technologies
Cerberus Division
e1148c
06.2000
In a CBS-3 up to six UART are available and so 18 dip-switches are reserved (Actually
only four of them are available). They are divided into groups of three. Each group can
assume the value corresponding to the subsystem you want connect.
SUBSYSTEM
DIP-SWITCHES
MSB
LSB
no subsystem
OFF
OFF
OFF
CS11/CZ10/CC60
OFF
OFF
ON
CS4/CZ12
OFF
ON
OFF
Tab. 2 Subsystem selection
UART
DIP-SWITCHES
MSB
LSB
1
S1.6
S1.5
S1.4
2
S2.4
S2.3
S2.2
3
S3.2
S3.1
S2.8
4
S3.8
S3.7
S3.6
Tab. 3 Association UART/subsystem
You must then set the communication baud rate according to the suggested proto-
col/baud rates (See section 6).
3.2.2
Cerban vitality telegram
The dip-switch S1-2 has the optional function to filter the Cerban vitality telegram; the
dip-switch is valid for all of the Cerban line which are defined on the gateway.
The only reason to filter the vitality telegram is to limit the traffic of messages to the
LMS station(s). Note that if the vitality check is enabled at LMS level, then this dip-
switch must be set to ON, else LMS will generate false fault events.
S1-2
Function
OFF
Vitality telegram filtered
ON
Vitality telegram not filtered
Tab. 4 Cerban vitality telegram filtering
3.3
Configuration by Flash EPROM
If you have the configuration EPROM, you have to set OFF the dip-switch S1-1. The
default configuration for this dip-switch set is for EPROM
not
installed, so you actually
have only to verify the settings.
Even if the Flash EPROM configuration is enabled, you must set the communication
baud rate with subsystems using the dip-switches and according to the suggested pro-
tocol/baud rates (See section 6).