4.12 Acoustics inhibition
This menu allows to disconnect momentarily the acoustics corresponding to the different events that can be
displayed. If the event that went off the acoustic reappears or a different one appears, then the acoustic will
be automatically activated.
The events with a corresponding acoustic are the following:
• Ventilation Level Acoustic –one per group- (1st and 2nd speed).*
• Alarm Level Acoustic –one per group-.
In the highest reading mode, the detector causing it will be displayed.*
• Saturation Acoustic: Equipment Bottom of scale for the different gases.*
• General Group Fault Acoustic: Group/s nº are displayed.
• Detector Error Acoustic: Detector/s nº are displayed.
• Sensor Error Acoustic: Detector/s nº are displayed.
• Power Fault Acoustic.
• Battery Fault Acoustic.
• WARNING, PRE-ALARM and ALARM acoustic with explosive gases.
* Just if the activated acoustics for these modes have been programmed.
1. Press
ACOUSTIC INHIBITION
to disconnect the acoustic signal while the event is displayed.
5. OPERATION MODE WITH EXPLOSIVE GASES -EXP-
The function of the
VENTILATION (AUTO/MAN/STOP)
push button will be limited to activate the different
electrovalves of gas cut in each group (Gr1 – Gr2) manually. It will be necessary the system to be in Pre-alarm
mode.
1. Press
VENTILATION
.
“Auto”
is displayed.
2. Press
VENTILATION
again.
“Menu”
is displayed.
3. Press
ENTER
to memorise.
5.1
Alarm levels
SIEMENS CC62P
includes 3 programmable alarm levels.
WARNING:
An acoustic signal goes off when the 10% L.E.L. is reached -default level programmed-.
PRE-ALARM:
An acoustic signal goes off and Relay 1 in Group 1 is activated when the 20% L.E.L. is reached
-default level programmed-.
ALARM:
An acoustic signal goes off and Relay 2 in Group 1 is activated when the 40% L.E.L. is reached -default
level programmed-.
Relays 3 and 4 will have the same functioning than the previously described for groups 1 and 2.
Содержание CC62P
Страница 2: ...Fire Security Products Siemens Building Technologies 03 2012 SiemensUserMan v03 2 2 ...
Страница 21: ...Fire Security Products Siemens Building Technologies 03 2012 SiemensUserMan v03 21 6 QUICK PROGRAMMING ...
Страница 31: ...Fire Security Products Siemens Building Technologies 03 2012 SiemensUserMan v03 31 6 PROGRAMAÇÃO RAPIDA ...
Страница 33: ......
Страница 34: ...Siemens Building Technologies SiemensUserMan vo3 ...