1) If less than 24V is present across the battery:

(a) Batteries are not accepting the charge

       OR

(b) Battery capacity is too large for the BC-35

and the number of BE-35s being used

2) If more than 30V is present across the battery:

(a) Batteries used have high internal impedance

                      OR

(b) BC-35 is not shutting off the charge state at

the required voltage point

If the BC-35 is not providing a charging current, test
pin 1 of the P1 plug on the BC-35 module in reference
to the negative side of the power supply. If there are no
volts at this point, replace the BC-35 module. If there
are more than 2 VDC at this point, and no alarm is
present, replace the CP-35 panel.

This information is provided to assist you in diagnosing
relatively routine problems. There may be extenuating
circumstances involved which are not covered here. If
further assistance is needed, please contact your Regional
Engineer or the Siemens Industry, Inc., Technical Support
Group.

WARNING:

The BC-35 has been factory set for the bat-
teries specified. Any alteration or adjust-
ment to this module will void both the UL
listing and the Manufacturer’s Warranty and
may cause damage to the battery.

P/N 315-086767-5

Содержание BC-35

Страница 1: ...roprietary The BC 35 charging circuit provides a charging current only if the voltage of the batteries being used is between 18 3 VDC and 27 7 VDC If the battery voltage is out of this range the BC 35 will automatically cut off its charging circuit CAUTION Disconnect the system power input before installing the BC 35 and or BE 35 cable connections The BC 35 module has a trouble signal for both hig...

Страница 2: ... and 2 below Step 2 may also be used to troubleshoot the BC 35 when a trouble condition is indicated Step 1 Test the batteries connected to the BC 35 module a Remove the battery leads b Test the open battery voltage it should be between 22 and 27 VDC c Reconnect the battery and test it under a load con dition If possible remove the AC power from the system and measure the battery voltage Activate ...

Страница 3: ...arging current is displayed if the battery voltage is between 18 3 VDC and 27 7 VDC Once the battery is fully charged a pulsed charging current is present on a periodic basis The time between pulses is determined by the rate of discharge due to the internal circuitry of the charger and the ability of the individual battery to accept and maintain the charge condition The constant charge current is ...

Страница 4: ...f the power supply If there are no volts at this point replace the BC 35 module If there are more than 2 VDC at this point and no alarm is present replace the CP 35 panel This information is provided to assist you in diagnosing relatively routine problems There may be extenuating circumstances involved which are not covered here If further assistance is needed please contact your Regional Engineer...

Отзывы: