background image

Installation

13

Building Technologies 

020_ATI5100_A6V10235012_a_en

Fire Safety & Security Products 

 

23.09.2009

8.2

 

Connecting cables 

It is recommended to use a cable type IYSTY (Twisted Pair) 2 x 2 x Ø 0.6 mm or 

larger diameter. 
1.

 

Insert the cable through the cable entry hole [

 10] in the base.  

2.

 

If necessary, carefully remove the breakout pieces [

 10] . 

3.

 

Connect the individual wires to the screw terminals. 

Connections 

 

Contact pin  Abbreviation Function 

A/+ 

RS485 

B/- 

RS485 

+ Vin 

- Vin 

5 to 10 

 

Not connected 

 

Attach the cable with a cable tie. 

Cable tie 

8.3

 

Mounting the base 

Make sure to mount the unit only on surfaces that are sufficiently hard and rigid. 
1.

 

Mark 3 holes for the mounting screws [

 10] and one for the tamper contact 

[

 10] . 

2.

 

Drill the holes and screw the base. 

Содержание ATI510

Страница 1: ...Building Technologies Fire Safety Security Products ATI5100 Intrusion Arming Terminal Installation ...

Страница 2: ...t and in the subject thereof By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was delivered to him ...

Страница 3: ...tandards and Guidelines 6 3 1 EU Directives 6 3 2 FCC 6 3 3 C Tick 7 3 4 UL Directives 7 4 Technical Data 7 4 1 Recommended Cable Specifications 8 5 Details for Ordering 9 6 Package Contents 9 7 Description of Equipment 9 7 1 Service Description 9 7 2 Product overview 10 7 3 Set Jumpers 11 8 Installation 12 8 1 Opening the housing 12 8 2 Connecting cables 13 8 3 Mounting the base 13 8 4 Mounting t...

Страница 4: ...nual For information on configuration refer to the SiPass integrated user manual Contacting us If you have questions or suggestions regarding the product or this documentation please contact our Customer Support Center Intranet Customer Support Center Internet Worldwide contacts Email fs support sbt siemens com Tel 49 89 9221 8000 Training courses Siemens Building Technologies Fire Safety Security...

Страница 5: ...tions before installing configuring operating the device Keep this document for reference Always pass this document on together with the product Liability claim Use only spare parts and accessories that have been approved by the manufacturer Danger of electrical shock on the open device Only qualified personnel should open the unit 2 2 2 Transport Damage during transport Keep the packaging materia...

Страница 6: ...Compatibility Compliance with the European Directive 2004 108 EC has been proven by testing according to the following standards Emitted interference EN 55022 class B Interference resistance EN 50130 4 3 2 FCC This equipment complies with the FCC Rules CFR 47 Part 15 Emission Class B limits This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to ...

Страница 7: ...ectives UL 294 Access control units not UL evaluated for Household or Commercial Burglary 4 Technical Data ATI5100 Tamper contact Integrated in housing Display LC 128 x 64 dots 4 lines with 16 characters per line Operating voltage 9 to 30 VDC Current consumption 35 to 82 mA 12 V Operating temperature 0 to 50 C Relative humidity 93 no dew Buzzer Integrated Sound level Different settings for alarms ...

Страница 8: ...r mm Wire Type Insulation Shield Jacket 5 2 6 3 RS485 8 4 28 7 x 36 0 6 Tinned Copper Foam Polyethylene Aluminium foil Polyester tape braided shield PVC 4 2 6 3 RS232 8 4 24 7 x 32 0 6 Tinned Copper Foam Polyethylene Aluminium foil Polyester tape no braid PVC 4 2 6 3 RS422 8 4 24 7 x 32 0 6 Tinned Copper Foam Polyethylene Aluminium foil Polyester tape no braid PVC 8 4 Solid Bare Copper RJ45 8 4 24...

Страница 9: ...ion of Equipment 7 1 Service Description The ATI5100 is an intrusion arming terminal that operates as a part of an integrated access control and security system The ATI5100 provides a local interface between an advanced access controller ACC and the cardholder to arm and disarm alarm areas The following diagram displays where the ATI5100 fits in the SiPass integrated architecture FLN Bus RS4 85 FL...

Страница 10: ...uct overview E F3 EOL A B I G F1 X3 D F2 A K2 K3 C H K1 L Product overview A Lugs G Screws for mounting B Printed circuit board H Screw for tamper contact C Screw terminal I Cable duct D Tamper switch K1 K3 Breakout pieces E Fixing screw for printed circuit board L Cable entry hole EOL Jumper X3 Jumper F1 F3 Lugs holding the PCB ...

Страница 11: ...2009 7 3 Set Jumpers Jumper Description Value EOL EOL TERMINATION FLN System Bus This link allows the RS485 bus communication channel to be terminated in lengthy comms lines more than 100 m EOL X3 1 2 Reset the ATI5100 retaining the unit s firmware Interrupt the power supply to the unit for 1 sec or Close X3 1 2 2 1 ...

Страница 12: ...ire Safety Security Products 23 09 2009 8 Installation 8 1 Opening the housing 1 Loosen the screws by a couple of turns Open unit 2 Push the lugs downwards and slightly lift the cover using a screwdriver 3 Lift the cover by approx 2 cm and push it upwards Unit is opened ...

Страница 13: ...the base 2 If necessary carefully remove the breakout pieces 10 3 Connect the individual wires to the screw terminals Connections Contact pin Abbreviation Function 1 A RS485 2 B RS485 3 Vin 4 Vin 5 to 10 Not connected Attach the cable with a cable tie Cable tie 8 3 Mounting the base Make sure to mount the unit only on surfaces that are sufficiently hard and rigid 1 Mark 3 holes for the mounting sc...

Страница 14: ...the housing 3 The two lugs on the base engage with the corresponding recesses in the cover 4 Tighten the two screws at the bottom of the unit and seal them using the supplied seals Close unit 8 5 Programming and firmware download The ATI5100 is programmed using SiPass integrated software via the AC5100 or using the standalone FLN Configurator application Please refer to the appropriate User s Manu...

Страница 15: ...ossed out wheeled bin symbol on the product means the product is covered by the European Directive 2002 96 EC The correct disposal and separate collection of your old appliance will help prevent potential negative consequences for the environment and human health It is a precondition for reuse and recycling of used electrical and electronic equipment For more detailed information about disposal of...

Страница 16: ...ity Products GmbH Co oHG Siemensallee 84 D 76181 Karlsruhe www buildingtechnologies siemens com 2009 Copyright Siemens Switzerland Ltd Technical specifications and availability subject to change without notice Document ID A6V10235012 Edition 08 12 2009 ...

Отзывы: