Chapter 4 - 7SR120 · Data Communications Definitions
© 2017 Siemens Protection Devices Limited
Chapter 4 - Page 31 of 84
Address
Value
30002
2400
On reception these two registers should be interpreted in the correct order as IEEE754 floating point
representation.
4.2.2 FP_32BITS_3DP
The FP_32BITS_3DP is a 32 bit integer fixed point value, containing 3 decimal places of information. It is used
to send a real value to 3 decimal places as an integer. For example, if the value in a device is 123.456 it will
be sent as 123456. As it is an integer, negative numbers are sent as 2's complement.
FP_32BITS_3DP & MODBUS
In this MODBUS implementation the 32 bit value is stored in 2 16 registers in Big-Endian format. As
an example, if we take the hex representation of 123456, we have 1E240h. Assume this is stored in
the registers 30001 and 30002, it would look as follows:
Address
Value
30001
1
30002
E240
On reception these two registers should be interpreted in the correct order as a 32 bit integer.
4.2.3 UINT32
The UINT32 is a signed 32 bit integer. As it is an integer, negative numbers are sent as 2's complement.
UINT32 & MODBUS
In this MODBUS implementation the 32 bit value is stored in 2 16 bit registers in Big-Endian format. As
an example, if we take the hex representation of -123456, in 2's complement, we have FFFE1DC0h.
Assume this is stored in the registers 30001 and 30002, it would look as follows:
Address
Value
30001
FFFE
30002
1DC0
On reception these two registers should be interpreted in the correct order as a 32 bit integer.
4.2.4 UINT16
The UINT16 is a signed 16 bit integer. As it is an integer, negative numbers are sent as 2's complement.
UINT16 & MODBUS
In this MODBUS implementation the 16 bit value is stored in a 16 bit register in Big-Endian format. As
an example, if we take the hex representation of 5678 we have 162Eh. Assume this is stored in the
register 30001, it would look as follows:
Address
Value
30001
162E
On reception this register should be interpreted as a 16 bit integer.
Содержание Argus 7SR11
Страница 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Страница 92: ...7SR11 7SR12 Description Of Operation Chapter 1 Page 88 of 88 2017 Siemens Protection Devices Limited ...
Страница 94: ...7SR11 7SR12 Settings Instruments Guide Chapter 2 Page 2 of 20 2017 Siemens Protection Devices Limited ...
Страница 114: ...7SR11 7SR12 Performance Specification 2017 Siemens Protection Devices Limited Chapter 3 Page 2 of 56 ...
Страница 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Страница 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Страница 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Страница 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Страница 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Страница 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Страница 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Страница 286: ...7SR11 7SR12 Commissioning and Maintenance Guide 2017 Siemens Protection Devices Limited Chapter 6 Page 2 of 72 ...
Страница 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Страница 405: ......