![Siemens AQS2700 Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/siemens/aqs2700/aqs2700_basic-documentation_374178018.webp)
Configurations
Push button configuration (QSA2700)
4
18 | 40
A6V11160936_en--_c
4.4 Push button configuration (QSA2700)
4.4.1 On-event addressing (Climatix
TM
controllers configuration)
On-event addressing is a rapid configuration approach working together with
Siemens Climatix
TM
controllers.
The sensor is wired and connected to the Climatix
TM
controller via Modbus.
Press the
button for
LED
Action
More details
1…5 s
Constant red Press and hold the button
5…10 s
LED off
Release the button
Entering the addressing mode, LED
flashes yellow for 30 s.
●
Address is set to 246
temporarily.
Communication is established
automatically when:
●
Baud rate is 19200 (default).
●
Format is 1-8-E-1 (default).
●
Address is 246.
Then:
●
Master writes the Modbus
parameters.
●
Master writes “1” into register
4x0768 ("Bus configuration
command”) to activate the
change.
After a successful pairing, the LED
flashes green for 60 s, then turns to
permanent green.
Otherwise, the LED turns back to its
original state.
LED flashes
yellow for
0…30 s
Short press the button to fix
the address to 246.
If the LED is flashing, a short press of
the push button fixes the address to
246.
The LED is off for 2 s, then turns
yellow for 2 s and then turns to
permanent green.
The address is 246.
Further configuration should be
carried out from controller side.
Enter addressing mode and
configuration workflow via
push button