background image

Document No. 538-863 
Installation Instructions  
October 10, 2011 

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and 
models as design improvements are introduced. APOGEE and Insight are registered trademarks of Siemens Industry, Inc. Other product or 
company names mentioned herein may be the trademarks of their respective owners. © 2011 Siemens Industry, Inc. 

Siemens Industry, Inc.  

Building Technologies Division 
1000 Deerfield Parkway 
Buffalo Grove, IL  60089-4513 
U.S.A. 

Your feedback is important to us. If you have 
comments about this document, please send them to

 

[email protected]

 

 

Document No. 538-863 

Printed in the U.S.A. 

Page 2 of 2

 

 

Internal Switch Settings  

Modem startup default speed is saved at 19200 bps in 
NVRAM (non-volatile memory). Modem will auto baud 
down to other serial speeds. If field panel connection is 
slower speed connect terminal emulator at slower 
speed before saving settings to NVRAM. 

Following dial-up default commands are changed from 
manufacturer’s factory default no flow control. 

ATZ3 

Load RAM with Factory Default Profile 0 (&F0) 

AT&A0 

Disable ARQ result codes 

AT&B1 

Fixed DTE data rate (fixed MMI Speed) 

AT&K0 

Disable data compression 

AT&M4 

Enable error control mode (NAVRAM 1) 

ATX0 

Modem uses basic response codes 

ATS7=40 

Modem waits 40 seconds for carrier 

AT&W1 

Save settings in NVRAM Profile 1  

AT&M0 

Disable error control mode (Profile 0) 

AT&W 

Save settings in NVRAM Profile 0  

ATY1 

Static Set Power Up Profile to NVRAM 1 

 

 

CAUTION: 

 

USR5686G does not support &H2 &I0 
software flow control between modems. 
Using &H2 results in auto change to &I2 
RS-232 software flow control. XON/XOFF 
characters in data stream will cause 
modem to disconnect, fail to connect or 
stop sending. Use only &H0 &I0 no flow 
control set by ATZ3. 

APOGEE Insight AutoDial Application 
overrides RAM (volatile memory) with 
hardware flow control settings and 
extended response codes. 

 

Online Commands

 

 

CAUTION: 

 

Factory default for USR5686G is ATY1 
(NAVRAM1) error checking which 
connects to modems with or without error 
checking. Earlier model default was ATY0 
(NAVRAM0) no error checking. 

To disable error checking command ATY0 
one time with DIP switch 7 UP and reset 
(ATZ) or power cycle modem. ATYn 
commands are non-volatile. 

For other commands refer to US Robotics 
documentation supplied with modem.

 

Field Panel Installation 

1. 

You are not required to turn off the field panel. 

2. 

Plug modular phone cord supplied between 
installed surge protector and modem telephone 
jack (RJ-11 port wall plug icon on bottom). 

3. 

Connect field panel communication port to 
modem connector (DB25F, PC icon on bottom of 
modem). 

4. 

Use data cable supplied with a modem kit or 
purchased separately. 

5. 

For USB only connect the USB to RS232 Adapter 
between the USB Host port and data cable DB9F 
end, connect right angle adapter between the 
data cable DB25M end and the modem DB25F 
connector. 

6. 

Tighten all cable and adapter retainers. 

7. 

Plug power adapter into modem power jack (plug 
icon) and into the enclosure outlet. 

8. 

Turn modem on and place in bottom of enclosure. 
If required secure in place with commercially 
available 3M™ Dual Lock™ All Weather 
Reclosable Fasterners. 

9. 

Refer to Start-up Procedures on InfoLink for the 
specific field panel and application used. If 
necessary Start-up APOGEE Insight AutoDial 
application. 

Field Panel modem installation is now complete. 

Workstation Installation 

1. 

Load Insight PC with supplied modem software. 

2. 

Connect serial data cable to the modem (DB25F 
connector labeled with a PC icon) and to the 
serial communication port on the workstation 
using appropriate modem cable (for PC RS-232 
DB9M port use 536-004 DB9F to DB25M cable). 

3. 

Plug the power adapter into the power jack on the 
modem (plug icon) and into protected outlet. 

4. 

Plug phone cord into phone jack (labeled with a 
wall plug icon) and other end into telephone 
transient suppressor jack. 

5. 

Turn on modem and start-up Workstation 
APOGEE™ Insight Dial-Up Application. 

Workstation modem installation is now complete.

 

Отзывы: