20
Application
Table P2-6 – Main Breaker Selection
Ampere Breaker
Maximum Interrupting Rating (kA)
Rating
Type
240V
480V
600V
Available Trip Values
BL
10
—
—
HBL
65
—
—
BQD6
65
10
10
100
ED4
65
25
—
15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
ED6
100
42
18
HED4
100
65
—
CED6
200
200
100
ED4
65
18
—
ED6
65
25
18
125
HED4
100
42
— 125
CED6
200
200
100
QJ2
10
—
—
QJH2
22
—
—
60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QJ2H
42
—
—
225
FD6,
FXD6
65
35
18
HFD6,
HFXD6
100
65
25
70, 80, 90, 100, 110, 125, 150, 175, 200, 225
CFD6
200
150
100
FD6,
FXD6
65
35
18
250 HFD6,
HFXD6 100
65
25
250
CFD6
200
150
100
JXD6, JD6
65
35
25
200, 225, 250, 300, 350, 400
400
HJD6, HJXD6
100
65
35
200, 225, 250, 300, 350, 400
SJD6
65
35
25
200, 300, 400
CJD6,SCJD6
200
200
100
200, 300, 400
LXD6
65
35
25
450, 500, 600
LD6
65
35
25
250, 300, 350, 400, 450, 500, 600
600
HLD6, HLXD6
100
65
35
250, 300, 350, 400, 450, 500, 600
SLD6,
65
35
25
300, 400, 500, 600
SHLD6
100
65
35
300, 400, 500, 600
CLD6, SCLD6
200
150
100
300, 400, 500, 600
Q
Interchangeable trip main breakers are mounted at top of panel only.
Q
Twin mounted subfeed breakers are mounted at bottom of panelboard only and adds 24" to the panel height.
Q
Subfeed breaker is mounted at bottom of panelboard only. 400 amp subfeed breaker adds 30" to the panel height.
Table P2-7 – Subfeed Breakers
Mounting Position
Maximum Interrupting
Breaker
When Used As Subfeed Breaker
Rating (kA) Symmetrical
Type
Vertical
Ampere Ratings For Load
240V AC
480V AC
600V DC
FD6
, FXD6
Twin
70 - 250
65
35
18
HFD6
, HFXD6 Twin
70 - 250
100
65
25
JD6
,
Q
JXD6
Single
200 - 400
65
35
25
HJD6
, HJXD6
Single
200 - 400
100
65
35
Panel Type No. of cct
Wire Size - Branch Neutral
Lugs
Quantities
18cct
#6 - 1/0 Cu or Al
18 x #6 & 3x 1/0
30cct
#6 only Cu or Al
16 x #6 (qty 2)
42cct
#6 - 1/0 Cu or Al
18 x #6 & 3x 1/0 (qty 2)
54cct
#6 - 1/0 Cu or Al
12 x #6 & 14 x 1/0 (qty 2)
#6 - 1/0 Cu or Al
12 x #6 & 14 x 1/0
#4 - #14 & #14-3/0 Cu or Al
36 x #4-14 & 6 X #14-3/0
78cct
#4 - #14 & #14-3/0 Cu or Al
36 x #4-14 & 6 X #14-3/0 (qty 2)
90cct
#4 - #14 & #14-3/0 Cu or Al
36 x #4-14 & 6 X #14-3/0 (qty 2)
102cct
#4 - #14 & #14-3/0 Cu or Al
36 x #4-14 & 6 X #14-3/0 (qty 2)
P2
66cct
Table P2-9A - Standard Branch Neutral Lugs for BL BQD6 and ED breakers