Table 1.  AEM2100 Connection Information. 

IP Addresses

 

AEM IP Address 

        .          .          . 

Subnet Mask 

        .          .          . 

Gateway IP Address 

        .          .          . 

DHCP Names 

AEM2100 Name 

 

Domain Name 

 

System Name and Addresses 

BLN System Name 

 

Field Panel Address 

 

Insight Address 

 

Installation 

1.  Place the AEM2100 on the bottom of the field 

panel enclosure. 

2.  Plug the Ethernet patch cable into the RJ45 

Ethernet port on the AEM2100.  

3.  Connect the other end of the Ethernet patch 

cable as follows: 

 

For normal installations, plug into the jack 

box inside the field panel. Skip to Step 6. 

 

For S1 Smoke Control plug into the surge 

suppressor (Figure 1). 

4.  Plug the surge suppressor green patch cable 

into the jack box inside the field panel.  

5.  Connect the surge suppressor ground wire.  
6.  Connect a serial cable to the AEM2100  

Channel 1 and Channel 2 serial ports. 

7.  Tighten the serial cable screws. 
8.  Plug the serial cable RJ-11 connectors into the 

following field panel ports (Figure 1): 
a.  Plug Channel 1 into the RJ-11 or RJ-45 

MODEM port.  

b.  Plug Channel 2 into the RJ-11 MMI port. 

NOTE: 

All RJ-45 MODEM or MMI/MODEM ports 

accept both 6-pin RJ-11 and 8-pin RJ-45 plugs. 

 

Figure 1.  AEM2100 Connections (Smoke Control 

Installation Shown). 

9.  Plug the AEM2100 power pack into the field 

panel service box outlet.  
Boot-up takes <10s with IP Address. See Table 

for an explanation of LED operation.  

10.  Secure loose wiring with cable ties and store 

these instructions in the literature pocket.  

The installation is now complete. 

Table 2.  AEM2100 LED Indicators. 

LED 

Operation 

Power/Diagnostic 

(Blue) 

Steady On = Power OK 

Blinking 2x = No DHCP response 

Blinking 2x = Setup Menu active 

RX Serial 1 

(Green) 

Off = No data activity 

Blinking = Data being received by AEM2100 

channel 1 from Controller Modem port 

TX Serial 1 

(Yellow) 

Off = No data activity 

Blinking = Data being transmitted from AEM2100 

channel 1 to Controller Modem port 

RX Serial 2 

(Green) 

Off = No data activity 

Blinking = Data being received by AEM2100 

channel 2 from Controller MMI port 

TX Serial 2 

(Yellow) 

Off = No data activity 

Blinking = Data being transmitted from AEM2100 

channel 2 to Controller MMI port 

Ethernet Link 

(Bi-color)

 

Off = No Ethernet link established 

Solid Yellow = 10Mbps Ethernet link established 

Solid Green = 100 Mbps Ethernet Link established 

Ethernet Activity 

(Bi-color)

 

Off = No data activity 

Blinking Yellow = Half Duplex data activity 

Blinking Green = Full Duplex data activity 

 