Installation Instructions 

Document No. 538-924  

October 10, 2019 

 

APOGEE Ethernet Microserver 2100 (AEM2100) 

 

 

Unrestricted Item Number: 538-924, Rev. AB

 

Page 1 of 2

 

Product Description 

The APOGEE® Ethernet Microserver 2100 (AEM2100) 

allows APOGEE field panel networks to communicate 

with Insight® workstations across an Ethernet. A 

second serial port independently connects to the MMI. 

The AEM2100 supports Autosensing, 10Base-T, 

100Base-TX, half and full duplex TCP/IP. 

Product Numbers 

538-997  AEM2100 115V (Includes two serial cables 

with RJ11 connectors and 100-240V 50/60 

Hz power supply with US 2-Prong plug) 

 

CAUTION: 

 

Only use the AEM2100 power pack 

with the AEM2100. Do not use the 

power pack with other devices. 

Expected Installation Time 

15 minutes 

Caution Notation 

CAUTION 

 

Equipment damage or loss 

of data may occur if you do 

not follow a procedure as 

specified. 

Required Tools 

  1/8-inch flat-blade screwdriver 

  Cable ties 

  Laptop computer 

Required Materials 

  538-900 AEM Accessory Kit for configuration 

  US 2-Prong line cord adapter for the country 

where installed if not US 115V. 

  AEM2100 Privileged Password, IP Address, 

Subnet Mask, Gateway IP Address or DHCP 

Name, and Domain Name 

 
 

Prerequisites 

  Ethernet wiring is pulled into the field panel 

and terminated with one of the following: 

  Certified Category 5 or higher wiring, 

outlets, and patch cables for 100Base-TX 

operation. 

  Category 3 minimum and RJ45 plug. 

  PNET1GB (Manufacturer APC) Surge 

Suppressor for S1 Smoke Control or 

industrial installations 

  The TCP\IP server on Ethernet wiring.  

  Field panel containing the AEM2100 is running 

APOGEE Firmware Revision 2.2 or later. 

  Computer defining the AEM2100 is running 

APOGEE Insight Revision 3.1.2 or later or 

DESIGO CC. 

NOTE: 

If an AEM BLN contains pre-APOGEE field 

panels, pre-APOGEE naming conventions 

must be used in the APOGEE field panel and 

Insight workstation. 

Pre-Installation Configuration 

 

CAUTION: 

 

Do not plug the Ethernet cable into the 

AEM2100 until the AEM2100 is configured 

with IP Addresses or DHCP Names.  

  Pre-Configure AEM2100 using Channel 1 and 

a 9-pin cable to PC or Laptop COM port at 

9600 bps, 8 data bit, 1 stop bit, no parity.  

Press “xxx” immediately after powering up 

AEM2100. Record and set server per Network 

Administrator instructions. 

  Record the fixed IP Address or DHCP Name and 

the System Name and Addresses in Table 1. 