Operating instructions
Œ•Ž
64
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
Changing detector PARAMETER SET
When is this
function used?
It is mainly used to temporarily switch detectors to a less sensitive setting, e.g. when work is be-
ing carried out (as alternative to the 'Renovation' operating mode).
Parameter sets
available
F
You will find a detailed list of the parameter sets available in the chapter "Detector parameter
sets" on page 121 (section "Basic system information
i
·
For interactive detectors only, and only if this function has been approved by the service en-
gineer.
·
Only security personnel may temporarily change parameter sets.
·
Attention: Each temporary adjustment is automatically reset when the station is restarted.
Operating ac-
cess
If you still don't have operating access when starting operation work, the release procedure is
automatically called up.
Changing pa-
rameter set
Perform the following steps to set another parameter set:
Step
Action
Result / Comment
1
Navigate
to the ELEMENT you want us-
ing:
<Operate..>
t
<Browse..>
t
<Browse FIRE DETECTION..>
- or -
<Browse EXTINGUISHING..>
t
<Select SECTION
¯
>
t
<Selected ZONE
¯
>
t
<Select ELEMENT
¯
>
The element functions are dis-
played
2
Press
softkey
<Parameter sets functions..>
3
Press
softkey
<CHANGE parameter set.>
4
Press
softkey
<Next parameter set.>
Repeat this step until the corre-
sponding parameter set is found
5
Press
softkey
<Set>
Implementation messages
'
Implementing ...
'
- and -
'
Implemented
'
Содержание AlgoPilot B3Q661