Siemens AH Series Скачать руководство пользователя страница 9

Siemens Building Technologies, Inc.

  

 

P84395-003 B 

Sheet 3 of 3    

 
 
 

 
 

 

 
 
 

Figure 5: 

+

-

(+)

(-)

-

+ TO NEXT APPLIANCE OR

END OF LINE

RESISTOR (EOLR)

FROM PRECEDING

APPLIANCE OR FIRE

ALARM CONTROL

PANEL (FACP)

 

 

A

FLUSH MOUNTING

4

4

4

4

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

BACKBOX 2.0" DEEP

STD. SINGLE-GANG

UNIVERSAL 

MOUNTING PLATE 

#6-32 SCREWS 

#6-20  SCREW 

 

B

FLUSH OR SURFACE MOUNTING

4

4

4

4

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

DEEP BACKBOX OR

4" SQ. X 1-1/2"

UNIVERSAL 

MOUNTING PLATE  

#8-32  SCREWS

#6-20  SCREW  

100mm SQ. X 37.5mm

EUROPEAN BACKBOX

 

 

Figure 6: 

 

C

FLUSH OR SURFACE MOUNT

4

4

4

4

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

DEEP BACKBOX

DOUBLE-GANG X 2-1/4"

#6-32   SCREWS  

UNIVERSAL 

MOUNTING PLATE  

#6-20  SCREW  

 

D

SURFACE MOUNT

4

4

4

4

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

#6-20  SCREW  

SURFACE BACKBOX

SHBBS

UNIVERSAL 

MOUNTING PLATE  

#8-32  SCREWS  

 

 

 

• 

AS-MC-C Appliance has in-out wiring 
terminals that accepts two #12 to #18 
American Wire Gauge (AWG) wires at 
each screw terminal.  Strip leads 3/8” 
inches for connection to screw terminals. 

• 

Break all in-out wire runs on supervised 
circuit supervision as shown in Figure 6.  
The polarity shown in the wiring diagrams 
is for the operation of the appliances.  The 
polarity is reversed by the FACP during 
supervision. 

MOUNTING PROCEDURES: 

1. 

This model can be flush mounted to a standard single-gang backbox (Figure A), 4” backbox (Figure B) or double-gang backbox (Figure C).  They 
can also be surface mounted to a 4” or 100mm backbox (Figure B), a double-gang backbox (Figure C) or a SHBBS surface backbox (Figure D).  
Mounting hardware for each mounting option is supplied.  For proper mounting, be sure to use the mounting screws supplied with the unit. 

2. 

The Universal Mounting Plate (UMP) must be oriented correctly when it is mounted to the backbox.  Turn the UMP so that the arrow above the 
words “Horizontal Strobe” points to the top side of the UMP. 

3. 

Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.  Do not pass additional wires 
(used for other than the signaling appliance) through the backbox.  Such additional wires could result in insufficient wiring space for the signaling 
appliance. 

4. 

When terminating field wires, do not use more lead length than required.  Excess lead length could result in insufficient wiring space for the 
signaling appliance.  Position the field wires in the backbox so that they use minimum space and produce minimum stress on the product.  This is 
especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing.   

5. 

Thread the 4 field wires through the opening of the UMP.  Mount the UMP to backbox. 

6. 

Connect 4 field wires to the AS-MC-C terminal block (polarity must be observed).  Bend the 4 field wires up 90

o

 at the connection to the terminal 

block. 

7. 

Carefully push the 4 field wires into the backbox through the opening of the UMP by hand. 

8. 

Hook the 2 slots on the inside wall of the AS-MC-C onto the 2 tabs of the UMP and screw the AS-MC-C to the UMP using the #6-20 screw 
supplied. 

 

WARNING: A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW, UNDER 

CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY.  STROBE REFLECTIONS IN A 
GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE.  TO MINIMIZE THIS POSSIBLE HAZARD, IT IS STRONGLY 
RECOMMENDED THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH 
EXCEEDS FIVE (5) Hz AT THE OPERATING VOLTAGE OF THE STROBES. IT IS ALSO STRONGLY RECOMMENDED THAT THE INTENSITY 
AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, STANDARDS, 
REGULATIONS, CODES AND GUIDELINES. 

 
The 15/30/75/95cd settings are Listed for use in sleeping or non-sleeping areas when installed in accordance with appropriate NFPA Standards and the 
AHJ. 
 

NOTE:

  This equipment has been tested and found to comply with the limits for a Class B digital appliance, pursuant to Part 15 of the FCC Rules.  

These limits are designed to provide reasonable protection against harmful interference in residential installation.  This equipment generates, uses and 
can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio 
communications.  However, there is no guarantee that interference will not occur in a particular installation.  If this equipment does cause harmful 
interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the 
interference by one or more of the following measures:  1) Reorient or relocate the receiving antenna,  2) Increase the separation between the 
equipment and receiver,  3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected, and  4) Consult the 
dealer or an experienced radio/TV technician for help. 

Содержание AH Series

Страница 1: ... FS 250 panel XLS panel or PAD 3 power supply with built in sync protocol synchronization of the continuous horn tone provides the temporal code 3 tone man dated by NFPA 72 simultaneously for all audible appli ances This ensures a distinct temporal code 3 pattern when 2 or more audibles are within hearing distance If not synchronized the temporal sound could overlap and not be distinctive At the s...

Страница 2: ...e Strobe intensity based on UL Standard 1971 Technical Information For complete technical information please consult the relevant installation sheets as well as the Siemens Compatibility Guide Model Number Order Code Wall Mount Ceiling Mount Mounting Options Agency Approvals UL ULC CSFM FM AS MC R 500 636010 X A B D E F G J N R X X AS MC W 500 636011 X A B D E F G J N R X X AS HMC R 500 636012 X A...

Страница 3: ...of circuit wiring by an FACP NOTE All Canadian installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems CAN ULC S524 01 and Canadian Electrical Code Part 1 Final acceptance is subject to authority having jurisdiction AHJ NOTE Refer to P N 315 096363 for the maximum number of appliances on a single notification appliance circuit SPECIFICATIONS Tabl...

Страница 4: ...SOUND OUTPUT SETTINGS To set the candela slide the switch to the desired setting The setting is indicated by the pointer and label visible on the bottom side of the lens Figure 1 Figure 2 Showing Location of Jumper Plug Back View 15 75 1 30 1 0 CANDELA POINTER BOTTOM VIEW CODE 3 HI MED LO CANDELA SLIDE SWITCH Factory setting is on Medium dB Code 3 or March Time and 15 candela WARNING THE CANDELA S...

Страница 5: ...wiring diagrams is for the operation of the appliances The polarity is reversed by the FACP during supervision MOUNTING PROCEDURES 1 This model can be flush mounted to a standard single gang backbox Figure A 4 backbox Figure B or double gang backbox Figure C They can also be surface mounted to a 4 or 100mm backbox Figure B a double gang backbox Figure C or a SHBBS surface backbox Figure D Mounting...

Страница 6: ...S INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH EXCEEDS FIVE 5 Hz AT THE OPERATING VOLTAGE OF THE STROBES IT IS STRONGLY RECOMMENDED THAT THE INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS STANDARDS REGULATIONS CODES AND GUIDELINES NOTE This equipment has been tested and found to comply with the limits for ...

Страница 7: ...or compatibility with standard reverse polarity supervision of circuit wiring by a FACP NFPA 72 ANSI 117 1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer higher intensity strobes within the same protected area NOTE Refer to P N 315 096363 for the maximum number of appliances on a single notification appliance circuit SPECIFICATIONS Table 1 UL Ratings Model Operating Voltage Spe...

Страница 8: ...O CANDELA SLIDE SWITCH Back View Factory setting is on Medium dB Code 3 or March Time and 15 candela THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH MAKE CERTAIN THAT IT CLICKS IN PLACE AFTER CHANGING THE CANDELA SETTING THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION THE AUDIBLE STRO...

Страница 9: ...ld wires in the backbox so that they use minimum space and produce minimum stress on the product This is especially important for stiff heavy gauge wires and wires with thick insulation or sheathing 5 Thread the 4 field wires through the opening of the UMP Mount the UMP to backbox 6 Connect 4 field wires to the AS MC C terminal block polarity must be observed Bend the 4 field wires up 90 o at the ...

Страница 10: ...ion signaling The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose NFPA 72 ANSI 117 1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer higher intensity strobes within the same protected area NOTE Refer to P N 315 096363 for the maximum number of appliances on a single notification appliance circuit SPECIFICATIONS Table 1 UL Ratings Model...

Страница 11: ...tting is indicated by the pointer and label visible on the bottom side of the lens Figure1 Figure 2 Showing Location of Jumper Plug 115 177 CANDELA POINTER BOTTOM VIEW CODE 3 HI MED LO CANDELA SLIDE SWITCH Back View Factory setting is on Medium dB Code 3 or March Time and 177 candela WARNING THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION WHEN CHAN...

Страница 12: ...uld result in insufficient wiring space for the signaling appliance 4 When terminating field wires do not use more lead length than required Excess lead length could result in insufficient wiring space for the signaling appliance Position the field wires in the backbox so that they use minimum space and produce minimum stress on the product This is especially important for stiff heavy gauge wires ...

Страница 13: ...itation Guidelines in using fewer higher intensity strobes within the same protected area NOTE Refer to P N 315 096363 for the maximum number of appliances on a single notification appliance circuit CAUTION NOT RECOMMENDED FOR USE AT REFRIGERATOR FREEZER DOOR ENTRANCES OR OTHER AREAS WITH PERSISTENT CONDENSATION SPECIFICATIONS Table 1 Models and Ratings UL Rated Strobe Candela cd Maximum RMS Curre...

Страница 14: ...NSTALLATION WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH MAKE CERTAIN THAT IT CLICKS IN PLACE AFTER CHANGING THE CANDELA SETTING THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION Figure 3 Jumper plug settings for High Medium Low and Code 3 or March Time Figure 4 Jumper plug setting for Continuous Horn SHOWN SET ON HIGH dB SHOWN SET ON MED dB SHOWN SET ON LOW dB HI MED LOW Use nee...

Страница 15: ... SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY STROBE REFLECTIONS IN A GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE TO MINIMIZE THIS POSSIBLE HAZARD SIEMENS STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH EXCEEDS FIVE 5 Hz AT THE OPERATING VOLTAGE OF THE STROBES SIEMENS ALSO STRONGLY RECOMMENDS THAT THE INTENSITY AND ...

Страница 16: ...y for fire evacuation signaling and not for any other purpose SPECIFICATIONS Table 1 UL ULC Listed Models and Ratings Maximum RMS Current AMPS DC FWR Model Operating Voltage Special Application Per UL 464 VDC VRMS ULC Voltage Range VDC VRMS Lo Med Hi Lo Med Hi AH 16 33 20 31 0 021 0 043 0 080 0 041 0 051 0 090 Available in red or white Table 1A ULC Current Ratings Average Current AMPS Model ULC Vo...

Страница 17: ...PPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE THEY ARE INSTALLED THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG IN ACCORDANCE WITH THESE INSTRUCTIONS SOUND OUTPUT SPL SETTINGS Figure 1 Showing Location of Jumper Plug CODE 3 HI MED LO Factory setting is on medium dB and code 3 or March Time Figure 2 Jumper plug settings for high medium low and code 3 or March T...

Страница 18: ...x Figure C They can also be surface mounted to a 4 square or 100mm backbox Figure B a double gang backbox Figure C or a SHBBS surface backbox Figure D 2 All models are equipped with a Universal Mounting Plate UMP 3 Mounting hardware for each mounting option is supplied For proper mounting be sure to use the mounting screws supplied with the unit 4 Conduit entrances to the backbox should be selecte...

Страница 19: ...her purpose SPECIFICATIONS Table 1 UL ULC Listed Models and Ratings Maximum RMS Current AMPS DC FWR Model Operating Voltage Special Application Per UL464 VDC VRMS ULC Voltage Range VDC VRMS Lo Med Hi Lo Med Hi AH R WP 16 33 20 31 0 023 0 049 0 090 0 046 0 057 0 096 Table 1A ULC Current Ratings 24VDC Models Average Current AMPS Model ULC Voltage VDC VRMS Lo Med Hi 20 0 016 022 039 24 0 019 029 056 ...

Страница 20: ... DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE THEY ARE INSTALLED THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG IN ACCORDANCE WITH THESE INSTRUCTIONS SOUND OUTPUT SPL SETTINGS Figure 1 Showing Location of Jumper Plug J1 and J1 AUD P83511 J2 J1 H M L C O D E 3 J2 J1 H M L D 3 E O C Factory setting is on Medium dB and Code 3 or March Time Figure 2 Jumper Plug Settings for High Medium Low dB Code...

Страница 21: ...ring space for the signaling appliance 7 Do not pass additional wires used for other than the signaling appliance through the backbox Such additional wires could result in insufficient wiring space for the signaling appliance 8 The knock out opening on the backbox is sized for a conduit and matching connector Be sure that a proper watertight conduit fitting is used to connect the backbox for outdo...

Страница 22: ...ling The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose NFPA 72 ANSI 117 1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer higher intensity strobes within the same protected area NOTE Refer to P N 315 096363 for the maximum number of appliances on a single notification appliance circuit SPECIFICATIONS Table 1 UL Ratings Model Operatin...

Страница 23: ...ROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS CANDELA AND SOUND OUTPUT SETTINGS To set the candela slide the switch to the desired setting The setting is indicated by the pointer and label visible on the bottom side of the lens Figure 1 Figure 2 Showing Location of Jumper Plug 135 185 CANDELA POINTER BOTTOM VIEW CODE 3 HI MED LO CANDELA SLIDE SWITCH BACK VIEW Factory setting is o...

Страница 24: ...he FACP during supervision MOUNTING PROCEDURES 1 This model can be flush mounted to a standard single gang backbox Figure A 4 backbox Figure B or double gang backbox Figure C They can also be surface mounted to a 4 or 100mm backbox Figure B a double gang backbox Figure C or a SHBBS surface backbox Figure D Mounting hardware for each mounting option is supplied For proper mounting be sure to use th...

Страница 25: ...N THE FIELD OF VIEW WHICH EXCEEDS FIVE 5 Hz AT THE OPERATING VOLTAGE OF THE STROBES SIEMENS ALSO STRONGLY RECOMMENDS THAT THE INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS STANDARDS REGULATIONS CODES AND GUIDELINES NOTE This equipment has been tested and found to comply with the limits for a Class B digital appliance pursuant to Part 15 o...

Отзывы: