9/10
Siemens Building Technologies
Fan coil controller for wall mounting ACR12
CE1N3573E
HVAC Products
17.08.2001
M1
3
A
C
23
0
V /
50
Hz
PE
L
N Q1 Q2 Q3
Q1
Q2
Q3
N
450 VA max.
3573
A
0
7
L
N
Technical data
Operating voltage L, N, PE
AC 230 V
±
10 %
Frequency
50 Hz
Power consumption
20 VA (without field devices)
Protective earthing PE must be connected
Max. cross-sectional aera per terminal
2 wires each with 1.5 mm
2
or 1 wire with 2.5 mm
2
Fan control Q1, Q2, Q3
AC 230 V
Q1 load
max. 230 VA (cos
ϕ
= 0.9)
Q2, Q3 load
max. 450 VA (cos
ϕ
= 0.9)
Electric heater Q14
AC 230 V
Load (max., purely resistive)
2850 VA (AC 230 V / 12,5 A)
Contact life (B10)**
100,000 switching cycles
Load (reduced, purely resistive)
1250 VA (AC 230 V / 5.5 A)
Contact life (B10)**
300,000 switching cycles
** B10 = number of switching cycles reached by at least 90 % of the relays
Valve control Y1, Y10
AC 230 V
Load
3.5 VA (one thermic actuator
per output)
Changeover- or return air sensor B2 - M
Voltage against earth
AC 230 V
Cable length max.
3 m
Temperature sensor
QAH11 (NTC Element)
!
Power supply
Electrical connections
Outputs