Installation Instructions

Model ACM-1
Audio Control Module

P/N 315-092083-10

Figure 1

ACM-1 PC Board

INTRODUCTION

The Model ACM-1 Audio Control Module
from Siemens Industry, Inc. is the master
control module for the MXLV audio system.
The module controls all Voice related func-
tions. It has two yellow LEDs—the TROUBLE
LED indicates ACM-1 troubles and the
TRANSMIT LED monitors network activity.
Refer to Figure 1 for the location of the
LEDs. (These troubles also appear on the
MKB-2 panel.)

ACM-1 has a supervised tone generator
which provides a variety of tones for use
with the system. Each system can have two
of the available tones. The tones are set
with CSG-M. If an application requires tone
backup, use the P6 connector on the
ACM-1 for the BTC-1 Backup Tone card.
(Refer to Figure 1.)

The ACM-1 occupies one network address.
The switch S102 shown in Figure 2 is used
to set the network address that was chosen
in CSG-M for the ACM-1 module.

OPERATIONS

1. The ACM-1 controls and supervises the

preamplifier circuit for the microphone
and wiring for the retractable cord. The
preamplifier circuit controls the volume
of any signal that enters the circuit.

2. When the microphone key is pressed,

the ACM-1 sends the preannounce tone
that was configured in CSG-M, making
the microphone the source for audio
channel 1.

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

Содержание ACM-1

Страница 1: ...e set with CSG M If an application requires tone backup use the P6 connector on the ACM 1 for the BTC 1 Backup Tone card Refer to Figure 1 The ACM 1 occupies one network address The switch S102 shown in Figure 2 is used to set the network address that was chosen in CSG M for the ACM 1 module OPERATIONS 1 The ACM 1 controls and supervises the preamplifier circuit for the microphone and wiring for t...

Страница 2: ...available in the System can be sent to this speaker if selected in CSG M 4 Three supervised riser circuits provide low power audio signals to the OCC 1 to be sent to power amplifiers The ACM 1 can also connect these risers to an auxiliary non emergency signal source for use in non emergency audio applications 5 The Audio Control module communi cates with the VSM 1 Voice Switch modules the VLM 1 Vo...

Страница 3: ...ion of the system enclosure a Mount the ACM 1 module on the back of the MKB 2 front panel below the ANN 1 module Check that the ribbon cable connector P1 is in the upper left corner of the board before mounting b With the board in that position place the module over the five threaded mounting spacers See Figure 2 c Fasten the module in place with the No 6 screws provided 2 When an MHD 3 is used in...

Страница 4: ...r by color tracers on the wires In Nos 1 and 2 below be sure the black tracer wire is close to the 1 1 To wire the ACM 1 in an enclosure that has an MMB or a PSR Refer to Figure 4 a Connect the long 15 ribbon cable P N 555 192238 from the MMB P8 or PSR 1 P5 to P5 on the ACM 1 b Connect the short 15 conductor ribbon cable P N 555 192242 from ANN 1 P3 to P4 on the ACM 1 c Connect the 14 conductor ri...

Страница 5: ...e ACM 1 b Connect the 50 conductor ribbon cable P N 555 192201 from TBM 2 P3 to P2 on the ACM 1 c Connect the 5 conductor wire cable P N 600 190220 from TBM 2 P2 to P3 on the ACM 1 For additional information on the MXL MXLV System refer to the MXL MXLV Manual P N 315 092036 ELECTRICAL RATINGS t n e r r u C e l u d o M C D V 5 e v i t c A A m 6 7 1 t n e r r u C e l u d o M C D V 4 2 e v i t c A A ...

Страница 6: ...XOXXX 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 XOOOOOXX XOOOOXOO XOOOOXOX XOOOOXXO XOOOOXXX XOOOXOOO XOOOXOOX XOOOXOXO XOOOXOXX XOOOXXOO XOOOXXOX XOOOXXXO XOOOXXXX XOOXOOOO XOOXOOOX XOOXOOXO XOOXOOXX XOOXOXOO XOOXOXOX XOOXOXXO XO...

Страница 7: ...7 ...

Страница 8: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Building Technologies Ltd Fire Safety Security Products 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada P N315 092083 10 ...

Отзывы: