Note: 

1. 

The NAC circuit shown in the diagram is the active state at terminal 1 and 2 of ABHW-4BZ. 

2. 

ABHW-4BZ terminals 5-6 are polarity insensitive. Line 1 and Line 2 can be either line of 
device loop. 

3. 

The wiring at NAC of FC2025/FC2050/FV2025/FV2050 and FC922/FC924/FV922/FV924 
shown in the diagram for ABHW-4BZ is Style Z (Class A) (no EOL needed). If Style Y (Class 
B) wiring used at NAC output, EOL (2.4K, 0.5W resistor) must be used. 

4. 

For the max load current and max cable resistance, refer to the specifications of FC2025/FC2050 
/FV2025/FV2050 and FC922/FC924/FV922/FV924. 

 

Figure 4.2  
Installation/Wiring Diagram for ABHW-4BZ Audible Base Powered by NAC of 
FC2025/FC2050/FV2025/FV2050 and FC922/FC924/FV922/FV924

 

 

 

Figure 5 
Installation/Wiring Diagram for ABHW-4BZ Audible Base Powered by Device 
Loop 

 

ABHW-4BZ

ABHW-4BZ

-

+

-

+

5

6

1b

1a

8

8

7

7

6

6

5

5

1

1

2

2

3

3

4

4

TO NEXT

ADDRESSABLE

DEVICE

LINE 1

LINE 2

LINE 2

LINE 1

FROM THE DEVICE LINE OF 

THE COMPATIBLE LISTED

 IN THE SPECIFICATION

NAC1
  2_-

NAC1
  2_+

NAC1
  1_-

NAC1
  1_+

per Periphery

NAC outputs

ABHW-4BZ

ABHW-4BZ

5

6

1b

1a

8

8

7

7

6

6

5

5

1

1

2

2

3

3

4

4

LINE 1

LINE 2

FROM DLC LOOP OF 

FIREFINDER-XLS SYSTEM 

 FC2005/FC901 SYSTEM

FC2025/FC2050/FV2025/FV2050 SYSTEM

SYSTEM

FC922/FC924/FV922/FV924 

 

5

6

1b

1a

Содержание ABHW-4BZ

Страница 1: ...loop are fully synchronized with FD UL detectors and also support RL HC RL HW remote lamp The ABHW 4BZ provides Steady Temporal 3 Temporal 4 Temporal 4 low power March time 120 and Canadian March time 30 ABHW 4BZ is fully compatible with all Siemens addressable detectors see Compatible detectors section and recognizes the detector type automatically Application note The ABHW 4BZ is a UL268 ULC S52...

Страница 2: ... Vdc External power 16 33 Vdc Supervisory current max From loop 250 µA From external 20 uA Alarm current RMS max Loop powered High dBA 7 5 mA Low dBA 4 5 mA External powered High dBA 8 0 mA Low dBA 3 5 mA Constraints 1 If the alarm current of ABHW 4BZ is energized by an external power supply any UL listed 24VDC regulated power supply including the aux power output of XLS FC2005 FC901 FC2025 FC2050...

Страница 3: ... Refer to APPENDIX A in this document to calculate the max number of loop powered ABHW 4BZ audible bases 5 The maximum device line resistance cannot exceed the maximum device line resistance specified in the compatible panels 6 T tapping of the notification appliance circuit is not allowed 7 The NAC output must be set to a steady DC if it is used for ABHW 4BZ Configuration Important The ABHW 4BZ m...

Страница 4: ...ase mounting 1 Route all wires out from the outlet box 2 When the alarm LED viewing is critical position the LED mark on the base in the intended direction Refer to Figure 8 3 Make connections directly to the audible base terminals located on the back of the base Refer to the related Installation Wiring diagram 4 After all bases are installed check loop continuity For ABHW 4BZ loop continuity chec...

Страница 5: ... Alarm Control Panels A6V10337045 FC922 FC924 FV922 FV924 Cerberus PRO 250 500 point Fire Alarm Control Panels A6V10356958 Compatible detectors FD UL series detectors table 1 Model Siemens Part Doc P N Type Description FDO421 S54320 F4 A1 A6V10323926 Desigo optical detector FDOT421 S54320 F6 A1 A6V10323934 Desigo optical heat detector FDT421 S54320 F5 A1 A6V10323930 Desigo heat detector FDOOT441 S...

Страница 6: ...sitive Line 1 and Line 2 can be either line of device loop 3 EOL device of HTRI 3 6K 1 4W resistor P N 140 820185 4 ABHW 4BZ can be wired either Style Z Class A or Style Y Class B 5 For the max load current refer to the specifications of the compatible panels listed in this document 6 The 24VDC regulated power supply could be the Aux Power Output from the compatible panels or from PAD 3 PAD 4 PAD ...

Страница 7: ...may also be wired as Style Y Class B 5 ZIC 4A Notification Appliance Circuits provide 4 outputs that can be configured for Class A or Class B Refer to the ZIC 4A Installation Instructions P N 315 033050 6 EOL resistor 24k ohms 1 2 watt 5 P N 140 820405 Figure 2 Installation Wiring Diagram for ABHW 4BZ Audible Base Powered by ZIC 4A NAC of FireFinder XLS System 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1...

Страница 8: ...nals 5 6 are polarity insensitive Line 1 and Line 2 can be either line of device loop 3 The wiring at NAC of FC2005 FC901 shown in the diagram for ABHW 4BZ is Style Z Class A no EOL needed If Style Y Class B wiring used at NAC output EOL 24K 0 5W resistor must be used 4 For the max load current and max cable resistance refer to the specifications of FC2005 FC901 Figure 4 1 Installation Wiring Diag...

Страница 9: ...2050 FV2025 FV2050 and FC922 FC924 FV922 FV924 Figure 4 2 Installation Wiring Diagram for ABHW 4BZ Audible Base Powered by NAC of FC2025 FC2050 FV2025 FV2050 and FC922 FC924 FV922 FV924 Figure 5 Installation Wiring Diagram for ABHW 4BZ Audible Base Powered by Device Loop ABHW 4BZ ABHW 4BZ 5 6 1b 1a 8 8 7 7 6 6 5 5 1 1 2 2 3 3 4 4 TO NEXT ADDRESSABLE DEVICE LINE 1 LINE 2 LINE 2 LINE 1 FROM THE DEVI...

Страница 10: ...DOOTC441 OP921 OH921 HI921 OOH941 and OOHC941 detectors 1 2 3 4 8 7 6 5 TO NEXT ABHW 4BZ DB 11 DB 3S or DB X3RS LINE 1 LINE 2 LINE 1 LINE 2 FROM DLC LOOP OF FIREFINDER XLS SYSTEM F 2005 F 901 SYSTEM FC2025 FC2050 FV2025 FV2050 FC922 FC924 FV922 FV924 C C SYSTEM SYSTEM JUMPER FOR TONE SELECTION ABHW 4BZ TO NEXT ABHW 4BZ DB 11 DB 3S or DB X3RS LINE 1 LINE 2 LINE 1 LINE 2 FROM DLC LOOP OF FIREFINDER ...

Страница 11: ...orks with H series detector Only External Powered can be used A fixed 85dB tone is provided and only 2 tones can be selected steady and Temporal 3 refer to Figure 6 Steady without a jumper at terminals 3 and 4 Temporal 3 terminals 3 and 4 are shorted with jumper 4 When use External Powered for alarm the ABHW 4BZ still takes some power from loop during both supervision and alarm status to keep it a...

Страница 12: ...nt in one loop under the worst case scenario with 50 Ω cable resistance I d is the total load current for the devices loaded in the loop Figure 9 Max number of loop powered ABHW 4BZ in high dBA Figure 10 Max number of loop powered ABHW 4BZ in low dBA Loop Powered ABHW 4BZ Low dBA 0 10 20 30 40 50 60 0 50 100 150 200 250 Load Current mA for ABHW 4BZ audible base quantity Number of ABHW 4BZ Loop Pow...

Страница 13: ...ne card at worst case from the user manual of the panel Example For DLC in XLS systems 252 H series devices can be loaded at the end of 50 ohms max line resistance the worst case and max load current is 252mA Imax Step 3 Find out the available load current I for loop powered ABHW 4BZ audible bases I Imax Id Example If 100 FDOT421 and 150 HFP 11 detectors loaded at the end of 50 ohms cable I 252 13...

Страница 14: ... machines and networks which should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures e g firewalls and or network segmentation are in place Additionally Siemens guidance on appropriate security measures should be taken into account For additional information please contact your Siemens sales r...

Отзывы: