Connecting to the I/O Card

 9510 and 9610 I/O Card

Page 4

Connecting to the I/O Card

See the 

9510 / 9610 Installation Guide

 for detailed instructions.

Verifying Operation

Checking Status on Front Panel

The 9510 / 9610 meter’s onboard status inputs and digital outputs can be 
monitored using the 

D Inputs

 and 

D-Output

 softkey items. Two additional 

softkey items have been added to monitor the status and values provided by the 
I/O card’s Analog Input and Analog Output ports. These menus are located in the 
main softkey list, and are named 

DI-I/O

 and 

Anlg-I/O

.

WinPM.Net Vista Diagram

The meter’s Vista screens have provisions for monitoring and altering the states of 
each I/O port. 

Testing Analog I/O Operation

Most analog devices (such as dial-type gauges) connected to your analog input 
and output ports allow you to see whether the port is delivering current. If your 
connected device cannot help you determine the port's operation, follow these 
steps:

1.

Ensure that the meter is properly configured. 

2.

Disconnect supply power from your meter and make sure that no static charge 
remains in the circuit.

3.

Place an ammeter in series with the port.

4.

Power up the meter, and measure the current.

If your analog ports are not producing the output current as expected, contact 
Customer Service.

Содержание 9510

Страница 1: ...arks are property of their respective owners Revision Date July 19 2004 9510 and 9610 I O Card This document describes how to install configure and verify the operation of the optional Input Output card I O card available for your 9510 9610 meter It supplements your meter s Installation Guide and User s Guide In This Document Installation and Wiring 2 Preparing the Meter for Installation 3 Install...

Страница 2: ... 8 digital inputs Depending on what you ordered the I O card will also contain either 4 analog inputs or 4 analog outputs or both Check the label on the I O card for your I O specifications AI4 AO4 AI3 A03 AI2 A02 AI1 AO1 Rear View of Meter Analog connections from external transducers 0 to 20 mA or 0 1 mA Analog Connections to analog transducers 0 to 20mA 500 Ohm load Max 1 to 1mA 10k Ohm load Max...

Страница 3: ...these steps to install the I O card 1 If present remove the plastic tab that seals the I O card s cover plate to the meter Use the Phillips screwdriver to remove the plate s two screws then remove the plate 2 Hold the I O card by the sides and slide it into the base unit with the component side facing up Slide the edge of the circuit board down the slots along each side of the chassis 3 Align the ...

Страница 4: ...O and Anlg I O WinPM Net Vista Diagram The meter s Vista screens have provisions for monitoring and altering the states of each I O port Testing Analog I O Operation Most analog devices such as dial type gauges connected to your analog input and output ports allow you to see whether the port is delivering current If your connected device cannot help you determine the port s operation follow these ...

Отзывы: