6 Storage
For the storage of delivered switchgear, parts of the switchgear, or accessories before
installation, select a suitable storage place.
WARNING
Transport units tipping over
If the storage spaces are overloaded, transport units can tip over and cause life-endangering
injury.
⇨ Observe the load-bearing capacity of the floor.
⇨ Do not stack the transport units.
WARNING
Fire risk
The transport unit is packed in flammable materials.
⇨ No smoking.
⇨ Keep fire extinguishers in a weatherproof place.
⇨ Mark the location of the fire extinguisher.
NOTICE
Consumed desiccant bags
Desiccant bags lose their effectiveness after 6 months. Consumed desiccant bags can lead to
the corrosion of switchgear parts and accessories. High air humidity due to consumed
desiccant bags can lead to the formation of creepage distances.
⇨ Have the desiccant bags replaced by a specialist every 6 months.
NOTICE
Outdoor storage
Outdoor storage of unpacked transport units can damage the switchgear or the accessories.
⇨ Preferably store transport units indoors.
⇨ Only store transport units outdoors in sea freight packing, covered, and in a
weatherproof place.
1. Observe the information provided on the switchgear packing and concerning transport and
storage.
-25°C
+55°C
10%
90%
106 kPa
50 kPa
Gerät darf nur senkrecht transportiert werden!
Unit must only be transported in vertical position!
Fig. 28:
Storage and transport information (example)
1
Transport and store in vertical
position
2
Fragile contents
3
Protect against moisture
4
Pressure
5
Humidity
6
Storage temperature, values de-
pending on ordered design
Содержание 8DJH