Technical data | 4
29/174
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
Motor operating mechanism
Tab. 18:
Rated currents of the motor protection equipment (protection equipment with tripping
characteristic type C):
Rated supply voltage [V]
Recommended rated current for the protection equipment [A]
24 DC
4
48 DC
2
60 DC
1.6
DC/AC 110 (50/60 Hz)
1.0
DC 120/125
1.0
DC 220
1.0
AC 230 (50/60 Hz)
0.5
The control voltage (including releases) is protected with 8 A.
Release
Releases trip the switch-fuse combination. The electrical opening command is transmitted to the
OPEN latch via a magnet armature by unlatching an energy store.
Depending on the operating mechanism used, up to 2 releases can be used.
▪
Shunt release (-Y1, -Y3)
Shunt releases (optional) are used to trip or electrically open the switch-fuse combination.
The opening command is executed by application of an auxiliary voltage (AC or DC,
depending on the design option).
After opening the switch-fuse combination, the release is de-energized internally.
Tab. 19:
Power consumption of the operating coils
Operating coil
Power consumption [W/VA]
Switch-fuse combination
Shunt release (-Y1, -Y3)
≤ 370
4.3 Three-position disconnector
Switching capacity and classification for disconnector and make-proof earthing switch according
to IEC/EN 62271-102 / VDE 0671-102:
Tab. 20:
Disconnector
Rated voltage U
r
kV
7.2
12
15
17.5
24
Rated normal current I
r
A
250, 630
Number of mechanical operating cycles /
classification
n
1000 / M0
Tab. 21:
Make-proof earthing switch
Rated voltage U
r
kV
7.2
12
15
17.5
24
Rated short-circuit making current I
ma
50 Hz
up to
kA
63
50/52.5
1)
60 Hz
up to
kA
65
52/55
1)
Number of short-circuit making operations / Classifi-
cation
n
5 / E2
1)
Design option