9 | Operation
136/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
9.2.6 Operating levers
Operating levers are available in different designs.
Fig. 175:
Universal operating lever, short
Universal operating lever (standard) with black handles
▪ Operation of switch-disconnectors, disconnectors and earthing switches
▪ Charging of operating mechanisms of circuit-breakers type 2 and switch-fuse combinations
Separate operating levers (option)
▪ Operating lever with black handles:
–
Operation of switch-disconnectors and disconnectors
–
Charging of operating mechanisms of circuit-breakers type 2 and switch-fuse
combinations
▪ Operating levers with red handles:
–
Operation of earthing switches
Long operating levers (option)
All operating levers are optionally available with
long
design. The long operating lever is
equipped with an additional spacing tube. Use of long operating levers:
▪ Switchgear in compact substations
▪ Switchgear with deep cable compartment cover
Anti-reflex levers
With anti-reflex levers, a direct inversion of the operating direction during a switching operation
is prevented. Each operating lever can be retrofitted to an anti-reflex lever:
1. Remove the setscrew
1
from the standard operating lever.
1
Fig. 176:
Retrofitting to an anti-reflex
lever
1
Setscrew
9.2.7 Hand crank
The hand crank is used for charging the spring energy store in panels with circuit-breaker
type 1.1.
Fig. 177:
Hand crank