7XT3400-0*A00/DD
English
C53000-B119U-C130-1
11
Limit values
Load capability of the 20Hz band-pass filter
Connections (1B1 - 1B4)
Permissible voltage, continuous
55 V ac
Permissible voltage for
≤
30 s
550 V ac
Frequency of superimposed ac voltage
≥
45 Hz
Overload capability, continuous
3.25 A ac
Test voltage
2.8 kV dc
Load capability of the voltage divider circuit
Connections (1A1 - 1A4):
Permissible voltage, continuous
55 V ac
Permissible voltage for < 30 s
550 V ac
Test voltage
2.8 kV dc
Permissible ambient temperatures
with RB <5
Ω
burden
≤
40 °C or
≤
104 °F
with RB >5
Ω
burden
≤
55 °C or
≤
131 °F
Note:
The device may produce up to 75 W power losses during service. In order to prevent
heat pockets, the dissipation of the losses must not be restricted. The minimum clearance
above and below the device to other units or walls is 100 mm or 4 inches. In cubicles, the
device shall be installed in the bottom area.