7SR224 Argus Description of Operation
5.5
Broken Conductor (46BC)
The element calculates the ratio of NPS to PPS currents. Where the NPS:PPS current ratio is above
46BC
Setting
an output is given after the
46BC Delay
.
The Broken Conductor function can be inhibited from
Inhibit 46BC
A binary or virtual input.
Figure 5.5-1 Logic Diagram: Broken Conductor Function (46BC)
5.6
Trip Circuit Supervision (74TCS)
The relay provides three trip circuit supervision elements.
One or more binary inputs can be mapped to
74TCS-n.
The inputs are connected into the trip circuit such that at
least one input is energised when the trip circuit wiring is intact. If all mapped inputs become de-energised, due to
a break in the trip circuit wiring or loss of supply an output is given.
The
74TCS-n Delay
setting prevents failure being incorrectly indicated during circuit breaker operation. This delay
should be greater than the operating time of the circuit breaker.
The use of one or two binary inputs mapped to the same Trip Circuit Supervision element (e.g. 74TCS-n) allows
the user to realise several alternative monitoring schemes – see ‘Applications Guide’.
Figure 5.6-1 Logic Diagram: Trip Circuit Supervision Feature (74TCS)