7SR157 Technical Manual
Chapter 4 - Page 38 of 58
© 2016 Siemens Protection Devices Limited
5.3 Point List
The tables below identify all the default data points provided by the implementation of the Triangle MicroWorks, Inc.
DNP 3.0 Slave Source Code Library.
This protocol can be set to use any or all of the relays hardware interfaces (USB, Fibre Optic, RS232 and RS485)
where fitted. The relay can communicate simultaneously on all ports regardless of protocol used.
The Station Address of the port being used must be set to a suitable address within the range 0 - 65534 to enable
communication. This can be set by the Communications Menu : COM n-xxxxx Station Address setting.
Communication via DNP3 over Ethernet requires external devices. Please refer to the documents TCPIP Catalogue
Sheet and TCPIP Interface Technical Guidance Notes for more information.
The information shown below is the default configuration. This can be modified using the Communications
Configuration Editor tool, refer
5.3.1 Binary Input Points
The default binary input event buffer size is set to allow 100 events.
Binary inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
1 Binary Input 1
0,2
2
2
2 Binary Input 2
0,2
2
2
3 Binary Input 3
0,2
2
2
4 Binary Input 4
0,2
2
2
5 Binary Input 5
0,2
2
2
6 Binary Input 6
0,2
2
2
35 Remote Mode
0,2
2
2
36 Out Of Service Mode
0,2
2
2
37 Local Mode
0,2
2
2
38 Local & Remote
0,2
2
2
45 General Start/Pick-up
0,2
2
2
46 VT Fuse Failure
0,2
2
2
207 Close Circuit Fail 1
0,2
2
2
208 Close Circuit Fail 2
0,2
2
2
209 Close Circuit Fail 3
0,2
2
2
210 Close Circuit Fail
0,2
2
2
225 General Alarm 1
0,2
2
2
226 General Alarm 2
0,2
2
2
227 General Alarm 3
0,2
2
2
228 General Alarm 4
0,2
2
2
Содержание 7SR157 Argus
Страница 1: ...Energy Management 7SR157 Argus Check and System Synchronising Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR157 Contents ...
Страница 58: ...7SR158 Technical Manual Chapter 3 Page 2 of 18 2022 Siemens Protection Devices Limited ...
Страница 76: ...7SR157 Technical Manual Chapter 4 Page 2 of 58 2016 Siemens Protection Devices Limited ...
Страница 80: ...7SR157 Technical Manual Chapter 4 Page 6 of 58 2016 Siemens Protection Devices Limited ...
Страница 92: ...7SR157 Technical Manual Chapter 4 Page 18 of 58 2016 Siemens Protection Devices Limited ...
Страница 122: ...7SR157 Technical Manual Chapter 4 Page 48 of 58 2016 Siemens Protection Devices Limited ...
Страница 124: ...7SR157 Technical Manual Chapter 4 Page 50 of 58 2016 Siemens Protection Devices Limited ...
Страница 126: ...7SR157 Technical Manual Chapter 4 Page 52 of 58 2016 Siemens Protection Devices Limited ...
Страница 150: ...7SR157 Technical Manual Chapter 5 Page 18 of 18 2018 Siemens Protection Devices Limited ...
Страница 161: ...Chapter 6 7SR157 Commissioning and Maintenance Guide Chapter 6 Page 11 of 14 2016 Siemens Protection Devices Limited ...
Страница 179: ...Siemens Protection Devices 1 ...