Function Control
Function control is used for:
•
Functions that do not contain stages or function blocks
•
Stages within functions
•
Function blocks within functions
i
i
NOTE
Simplifying functions and function control will be discussed in the following. The description also applies
to tripping stage control and function block control.
Functions can be switched to different operating modes. You use the parameter
Mode
to define whether you
want a function to run (
On
) or not (
Off
). In addition, you can temporarily block a function or switch it into test
mode for the purpose of commissioning (parameter
Mode
=
Test
).
The function shows the current status – such as an
Alarm
– via the
Health
signal.
The following explains the different operating modes and mechanisms and how you set the functions into
these modes. The function control is shown in
. It is standardized for all functions. Therefore, this
control is not discussed further in the individual function descriptions.
[losteurg-040411-01.tif, 1, en_US]
Figure 2-8
General Control of a Function
State Control
You can control the state of a function via the parameter
Mode
and the input
Superordinate state
.
You set the specified operating state of the function via the parameter
Mode
. The function mode can be set to
On
,
Off
, and
Test
. The operating principle is described in
Mode
via:
•
DIGSI 5
•
On-site operation at the device
•
Certain systems control protocols (IEC 61850, IEC 60870-5-103)
The possibility to adjust the superordinate state is limited. For test purposes, the complete device can set into
test mode.
2.3
Basic Structure of the Function
2.3 Function Control
SIPROTEC 5, Overcurrent Protection, Manual
53
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...