7SG11 Argus 1 Diagrams and Parameters
©2010 Siemens Protection Devices Limited
P20008 Page 11 of 33
Section 2: Settings
Relay Type
Serial Number
Substation
Feeder
Identity
Notes on Tables
All settings found in the Argus 1 relay types are listed below. Within the list some settings (indicated with greyed
cells) are not always visible, for the following reasons:
•
Depending on the version of the relay, a particular function and hence its related settings may not be present,
e.g. on a 2 phase-fault and SEF relay any settings related to earth-fault will not be present.
•
Depending on the value of some settings, other settings will be hidden, e.g. if the main characteristic is set to
DTL, rather than an IDMT characteristic, the time multiplier setting will be hidden and replaced by a time delay
setting.
Some settings in the tables show text in square brackets, e.g. ‘[SEF/REF] Current Setting’. This indicates different
text that may be displayed, depending on the value of other settings, i.e. ‘SEF Current Setting’ or ‘REF Current
Setting’ dependent on the value of the ‘Earth Fault Mode Select’ setting.
The second column in the tables (‘Ref’) provides a reference to the section in the Technical Reference
(publication P20007 issue 2004/02) that describes the setting.
The third column is left blank to allow users to complete the table with applied settings.
System Config. Menu
Setting name Ref Applied
value
Active Settings Group
2.2.1
Settings Group Edit/View
2.2.1
Copy Group
2.2.1
Power System Frequency
2.2.2
Hz
Set Pole B Type
2.2.3
Earth Fault Mode Select
2.2.3
P/F Rating (In)
2.2.3
A
E/F Rating (In)
2.2.3
A
[SEF/REF] Rating (In)
2.2.3
A
P/F CT Ratio
2.2.3
E/F CT Ratio
2.2.3
[SEF/REF] CT Ratio
2.2.3
Current Display
2.2.3
Set Identifier
2.2.4
Set Alarm 1
2.2.5
Set Alarm 2
2.2.5
Set Alarm 3
2.2.5
Setting name Ref Applied
value
Set Alarm 4
2.2.5
Set Alarm 5
2.2.5
Calendar – Set Date
2.2.7
Clock - Set Time
2.2.7
Clock Sync. From Status
2.2.7
Default Screen Timer
2.2.8
Change Password
2.2.9
Protection Menu
Setting name Ref Applied
value
Gn P/F Charact. Setting
2.3.1
xin
Gn P/F Charact.
2.3.1
Gn P/F Charact. Time Mult
2.3.1
Gn P/F Charact. Delay
2.3.1
sec
Gn P/F Lowset Setting
2.3.2
xIn
Gn P/F Lowset Delay
2.3.2
sec
Gn P/F Highset1 Setting
2.3.2
xIn
Gn P/F Highset1 Delay
2.3.2
sec