background image

 

Siemens Protection Devices Limited     

  

                  2 

7PG17– XR151/2/3

 

Supervision  Relays

 

 
 

 

 

Supervision relays XR151, 152 & 153 are attracted arma-
ture relays developed from the AR series: 
 
XR151 Trip relay supervision - Hand or Self reset flag. 
XR152 Protection supply supervision - Self reset flag 
XR153 Protection supply supervision - Hand reset flag 
 
 

 

 
The commissioning and future maintenance of this 
equipment should only be carried out by skilled personnel 
trained in protective relay operation and capable of ob-
serving all the necessary safety precautions and regula-
tions appropriate to this equipment and also the associ-
ated primary plant. 
 
Equipment should be isolated from auxiliary supplies and 
the circuit breaker trip circuit prior to commencing any 
work on an installed product. 
 

 

 
On receipt unpack the relay and inspect for any obvious 
damage. 
 
If damage has been sustained a claim should immediately 
be made against the carrier, also inform Siemens Protec-
tion Devices Limited. 
 
When not immediately required return the relay to its 
carton and store in a clean, dry place. 
 
 
 
 
Check that the relay operating voltage is correct for the 
auxiliary voltage to be used. In some instances relays are 
to be used with the coil in series with a voltage dropper 
resistor, this is advised on our Order Acknowledgement 
and shown on the relay label as "+Ext R", suitable resis-
tors are supplied with the relay, ensure that such resistors 
are mounted vertical, are secure and wired to the correct 
relay coil. 
 
If the relay is wired into the circuit isolate from the auxil-
iary supply by removing fuses and links as necessary. 
 

Physically check the wiring to the relay terminals for se-
curity and that is correct to the circuit schematic/wiring 
diagrams. 
 
 
 
 
 
Using a 500V insulation test set: 
 
a) Connect all relay terminals together and measure the 
resistance to earth 
 
b) Connect the d.c. input terminals together and measure 
the resistance between these terminals and all other 
terminals connected together and to earth. 
 
c) Connect the relay output contacts together and meas-
ure the resistance between these terminals and all other 
terminals connected together including earth. 
 
A value of 2.5 to 3.0 megohms obtained from the above 
tests is considered satisfactory, a value of less than 1.0 
megaohm is not satisfactory and the cause of such a low 
reading should be determined and corrected. 

 

 
 
 
 
 
It should not be necessary to adjust settings during rou-
tine tests unless parts have been replaced or other repairs 
carried out.  Adjustment of one setting will often influ-
ence another, therefore all settings must be checked after 
the final adjustment.   
 
The table of Mechanical Settings provides the basic set-
tings necessary before finally setting the relay to obtain 
its performance and are generally minimum values. 
 
 
 
 
 
 
Contact tips are fine silver on copper and should only be 
burnished if any pitting has occurred. Contact pressures 
are set by gentle pressure with contact setting pliers 
near to the contact stack assembly.  During this operation 
avoid putting any stress on the contact actuating cone. 
Contact pressures should be measured using an 
accurate gram gauge at the tip of the contact leaf. 
 
 
 
 
 
 
 

 
 

Description 

Unpacking, handling & storage   

Safety 

Preliminary Tests 

Insulation Tests 

Mechanical Settings 

Contacts 

Содержание 7PG17-XR151

Страница 1: ...Answers for energy 7PG17 XR 151 2 3 Supervision Relays Reyrolle Protection Devices ...

Страница 2: ...auxil iary supply by removing fuses and links as necessary Physically check the wiring to the relay terminals for se curity and that is correct to the circuit schematic wiring diagrams Using a 500V insulation test set a Connect all relay terminals together and measure the resistance to earth b Connect the d c input terminals together and measure the resistance between these terminals and all other...

Страница 3: ...Siemens Protection Devices Limited 3 ...

Страница 4: ...ure go fully home XR151 Operating Range D C relays 70 115 of rated voltage Relays must reset when the applied voltage is reduced to not less than 26 of rated voltage XR152 153 Operating Range D C relays 70 115 of rated voltage Relays must reset when the applied voltage is reduced to not less than 26 of rated voltage Electrical Tests ...

Страница 5: ...Siemens Protection Devices Limited 5 XR151 with Self Reset Trip Relays XR151 with Latched Trip Relays Application Diagrams ...

Страница 6: ...Siemens Protection Devices Limited 6 XR152 XR153 Please note These diagrams are for reference only the relay connection diagram for the specific device purchased should always be consulted ...

Страница 7: ...49 180 524 70 00 Fax 49 180 524 24 71 Charges depending on provider E mail support energy siemens com Power Distribution Division Order No C53000 G7076 C60 1 Printed in Fürth Printed on elementary chlorine free bleached paper All rights reserved Trademarks mentioned in this document are the property of Siemens AG its affili ates or their respective owners Subject to change without prior notice The...

Отзывы: