![Siemens 6SL3860 Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/siemens/6sl3860/6sl3860_reference-manual_378130019.webp)
Test procedure
1. The housing degree of protection is identified based on what is stamped on the rating plate.
2. Depending on the version, the following components are visually checked, e.g.:
– Canopies
– Cooling slots
– Fittings and rubber seals in the doors and between the cabinet units
– Cable entries
– Openings for water pipes, if available
– Additional components, if available
Result
The test is passed if the components required for the specified housing degree of protection are
available.
3.1.3
Electrical cabinet components
Fundamentals
A visual inspection is made to see whether the electrical cabinet components are installed as
defined in the layout diagram and/or circuit diagram.
Test procedure
1. The customer selects electrical cabinet components by random sampling.
2. The selected electrical cabinet components are visually checked to ensure that they are
correctly installed and marked.
Result
The test is passed if the selected electrical cabinet components are installed as specified in the
layout diagram and/or circuit diagram.
3.1.4
Cable installation
Fundamentals
Visual and mechanical checks are made to ensure that cables and conductors have been
installed correctly and are connected correctly according to the circuit diagram.
Tests
3.1 Visual inspection
SINAMICS SL150 6SL3860 F03 F70 F98 F79 F76
Reference Manual Rev.201902141425 SL150 luftgekühlt