Technical Data
Siemens AG
6SE7087-8NP87-0FB0
SIMOVERT MASTERDRIVES
Operating Instructions
6-3
Use shielded motor cable!
Length of motor cable:
≤
30 m
The shield of the motor cable is to be connected to the shielding sheet
and to the motor housing.
In accordance with the outputs of the units and their possible
combination with additional DC units, the radio-interference filters are
assigned to the converters as follows:
♦
If inverters are also connected to the Compact PLUS converter, the
radio-interference filter must be correspondingly larger.
♦
It is only permitted to use the filters in conjunction with the following
units:
EMC filter
Order No.
Compact PLUS converter
Order No.
Compact converter
Order No.
Rated current
6SE7012-0EP87-0FB0
6SE7011-5EP50
-
2 A
6SE7016-0EP87-0FB0
6SE7013-0EP50
6SE7015-0EP50
6SE7016-1EA51
6 A
6SE7021-2EP87-0FB0
6SE7018-0EP50
6SE7021-0EP50
6SE7018-0EA51
6SE7021-0EA51
12 A
6SE7021-8EP87-0FB0
6SE7021-4EP50
6SE7022-1EP50
6SE7021-3EB51
6SE7021-8EB51
18 A
WARNING
Assignment of units