shows the tripping stage release for the 1st automatic reclosing cycle. With available automatic
reclosing functions, the tripping stage release typically occurs up to the expiration of the dead time. The cycle
number in this state is on 1. However, if the automatic reclosing cycle is set only for 1-phase
25
, the tripping
stage release will be reset to the beginning of the 1-phase dead time. This is necessary, since every additional
evolving fault that occurs within the dead time causes a 3-pole cut-off, and subsequently, the automatic
reclosing function can no longer take place.
[lo1awezk-170912-01.tif, 1, en_US]
Figure 7-39
Stage Release for Protection Functions in the 1st Automatic Reclosing Cycle
The tripping stage release for higher automatic reclosing cycles is set to the beginning of the reclaim time for
rising edge close commands. Simultaneously, the cycle number is increased. The reset condition is identical to
the condition for the 1st automatic reclosing cycle. If the reduced dead time (RDT) mode is selected and no
additional reduced dead time occurs, the release of the 2nd cycle will be maintained, since it can be assumed
that the opposite end is open.
[lo2awezk-170912-01.tif, 1, en_US]
Figure 7-40
Stage Release for Protection Functions Starting With the 2nd Automatic Reclosing Cycle
Dead Time for Operating Modes With Tripping
In the Dead time function block, that dead time which corresponds with the previous trip command is started.
After expiration of the dead time, the automatic reclosing function changes to the status Switch on.
shows the dead time logic.
There are the following time stages that can be set differently:
•
Dead time after 3-pole tripping
•
Dead time after 1-pole tripping (only available for applications with 1-pole tripping)
•
Dead time after evolving fault
7.2.4.11
25
not for devices with only 3-phase tripping
Protection and Automation Functions
7.2 Automatic Reclosing Function
560
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...