Directional Time-Overcurrent Protection, Phases
Setting Values for the Function
Rotation angle of the reference
voltage
-180
o
to +180
o
Increments of 1
o
Setting Values for All Stage Types
Directional mode
Forward
Backward
–
Method of measurement
Fundamental component
RMS value
–
Threshold value
62
1 A @ 50 and 100 Irated
0.030 A to 35.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.15 A to 175.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
Increments of 0.001 A
Setting Values for the Definite Time-Overcurrent Protection Stage Type
Dropout ratio
0.90 to 0.99
Increments of 0.01
Time delay
0.00 s to 60.00 s
Increments of 0.01 s
Dropout delay
0.00 s to 60.00 s
Increments of 0.01 s
Setting Values for the IEC/ANSI Characteristic Curve Stage Type (Inverse-Time)
Type of characteristic curve
Characteristic curves according to IEC (see
(see
)
Dropout
Disk emulation
Instantaneous
–
Time multiplier
0.00 to 15.00
Increments of 0.01
Minimum time of the curve
0.00 to 1.00 s
Increments of 0.01 s
Additional time delay
0.00 to 60.00 s
Increments of 0.01 s
Dropout Ratio for the IEC/ANSI Characteristic Curve Stage Type (Inverse-Time)
Disk emulation
Approx. 0.90 * threshold value
Time multiplier
Approx. 1.05 * threshold value
Approx. 0.95 * pickup value
Setting Values for Stage Type with User-Defined Characteristic Curve (Inverse Time)
Time multiplier
0.05 to 15.00
Increments of 0.01
Number of value pairs for the operate
characteristic curve
2 to 30
Increments of 1
X values of the operate curve
1.00 to 66.67 p. u.
Increments of 0.01 p.u.
Y values of the operate curve
0.00 s to 999.00 s
Increments of 0.01 s
Number of value pairs for the dropout
characteristic curve
2 to 30
Increments of 1
X values of the dropout characteristic
curve
0.05 to 0.95 p. u.
Increments of 0.01 p.u.
11.10
62
If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 l
rated,sec
.
Technical Data
11.10 Directional Time-Overcurrent Protection, Phases
SIPROTEC 5, High-Voltage Bay Controller, Manual
1133
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...