External Trip Initiation
Setting Values
Tripping delay
0.00 s to 60.00 s
Increments of 0.01 s
Times
Operate time with time delay = 0 ms
- At initiation via binary input signal
Approx. 10 ms + OOT
38
.
Tolerance
Sequence tolerance for delay times
1 % of the setting value or 10 ms
11.7
38
Technical Data
11.7 External Trip Initiation
1110
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017