Standard mappings 3-1 and 3-3
61
SIPROTEC PROFIBUS DP - Bus mapping 6MD662/3/4
C53000-L1840-B011-03
3.2.1.4
Control Authority
3.2.2
Measured values
•
Ref. to chap. 2.3.2 for notes regarding scaling of measured values.
3.2.3
Metered measurands
•
Ref. to chap. 2.3.3 for notes regarding routing and scaling of metered measurands.
Offset
Designation of the SIPROTEC objects
Comments
Internal
object no.
9 / 5
Cntrl Auth
Control authority
(0 = REMOTE, 1 = LOCAL)
-
9 / 6
ModeLOCAL
Control mode LOCAL
(0 = LOCKED, 1 = UNLOCKED)
-
9 / 7
ModeREMOTE
Control mode REMOTE
(0 = LOCKED , 1 = UNLOCKED)
-
Offset
Designation of the
SIPROTEC objects
Comments
Scaling
(32767 corresponds to ...)
Transmission
as
10
3P1_V1 =
3P1 Phase to Earth Voltage V1
3276.7
Primary value
12
3P1_V2 =
3P1 Phase to Earth Voltage V2
3276.7
Primary value
14
3P1_V3 =
3P1 Phase to Earth Voltage V3
3276.7
Primary value
16
3P1_I1 =
3P1 Phase Current I1
3276.7
Primary value
18
3P1_I2 =
3P1 Phase Current I2
3276.7
Primary value
20
3P1_I3 =
3P1 Phase Current I3
3276.7
Primary value
22
3P1_P =
3P1 Active Power Three Phase
3276.7
Primary value
24
3P1_Q =
3P1 Reactive Power Three Phase
3276.7
Primary value
26
3P1_f =
3P1 Frequency
3276.7
Primary value
28
3P1_cosPhi =
3P1 Active Power Factor Three Phase
32.767
Primary value
Offset
Designation of the
SIPROTEC objects
Comments
Scaling
(2
31
-1 corresponds to ...)
Internal
object no.
30
<user-defined>
not pre-allocated
2
31
-1 impulses
-
34
<user-defined>
not pre-allocated
2
31
-1 impulses
-
38
<user-defined>
not pre-allocated
2
31
-1 impulses
-
42
<user-defined>
not pre-allocated
2
31
-1 impulses
-
Содержание 6MD662
Страница 6: ...Preview 6 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Страница 8: ...Revision index 8 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Страница 12: ...Table of contents 12 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Страница 72: ...Standard mapping 3 2 72 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Страница 86: ...Index 86 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...