4
Connecting up
WARNING
Danger due to lightning strikes
Antennas installed outdoors must be within the area covered by a
lightning protection system. Make sure that all conducting systems
entering from outdoors can be protected by a lightning protection
potential equalization system.
When implementing your lightning protection concept, make sure
you adhere to the VDE 0182 or IEC 62305 standard.
Suitable lightning conductors are available in the range of accessories
of SIMATIC NET Industrial WLAN:
•
Lightning protector LP798-1N
(article number 6GK5798-2LP00-2AA6)
•
Lightning protector LP798-2N
(article number 6GK5798-2LP10-2AA6)
Note
We recommend that you use the maintenance-free lightning protector
LP798-2N.
Exception
: When there is also DC power supplied via the antenna
cable. In this case, only use the lightning protector LP798-1N.
WARNING
Danger due to lightning strikes
Installing this lightning protector between an antenna and a
SCALANCE W device is not adequate protection against a lightning
strike. The lightening protectors mentioned above only works within
the framework of a comprehensive lightning protection concept. If
you have questions, ask a qualified specialist company.