Interface module IM 157-1 PN (6ES7157-1AB00-0AB0) 

25

 

Manual, 12/2016, A5E32347036-AD 

 

Parameters 

4.1

 

Parameters 

The following table shows the parameters for the IM 157-1 PN interface module. 

Table 4- 1 

Parameters (GSD file) 

Parameters 

Value range 

Default 

Efficiency range 

Configuration control 

 

Disable 

 

Enable 

Disable 

ET 200AL 

4.2

 

Explanation of the parameters 

Configuration control 

You can use this parameter to enable the configuration control function in the ET 200AL 

distributed I/O system. 

 

 

Note 
If you configure the enable, the ET 200AL distributed I/O system requires a control data 

record 196 from the user program in order for the ET 200AL distributed I/O system to 

operate the I/O modules. 

 

Reference 

You will find more information in the section Configuration control (option handling) and in 

the STEP 7 online help. 

 

Содержание 6ES7157-1AB00-0AB0

Страница 1: ......

Страница 2: ...____ ___________________ ___________________ SIMATIC ET 200AL Interface module IM 157 1 PN 6ES7157 1AB00 0AB0 Manual 12 2016 A5E32347036 AD Preface Documentation guide 1 Product overview 2 Wiring 3 Parameters 4 Interrupts error messages diagnostics and system alarms 5 Technical specifications 6 Dimension drawing A Cycle times B ...

Страница 3: ... only by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens p...

Страница 4: ...ly maintain a holistic state of the art industrial security concept Siemens products and solutions only form one element of such a concept Customer is responsible to prevent unauthorized access to its plants systems machines and networks Systems machines and components should only be connected to the enterprise network or the internet if and to the extent necessary and with appropriate security me...

Страница 5: ... block diagram 21 3 2 Pin assignment 22 4 Parameters 25 4 1 Parameters 25 4 2 Explanation of the parameters 25 5 Interrupts error messages diagnostics and system alarms 26 5 1 Status and error displays 26 5 2 Interrupts 29 5 2 1 Evaluating interrupts 29 5 2 2 Trigger a diagnostics interrupt 29 5 2 3 Triggering a hardware interrupt 30 5 2 4 Triggering an insert remove module interrupt 30 5 3 Alarms...

Страница 6: ...manuals contain a compact description of the module specific information such as properties terminal diagrams characteristics and technical specifications General information The function manuals contain detailed descriptions on general topics regarding the SIMATIC ET 200AL distributed I O system e g diagnostics communication Motion Control Web server You can download the documentation free of cha...

Страница 7: ...a for your CAx or CAe system You configure your own download package with a few clicks In doing so you can select Product images 2D dimension drawings 3D models internal circuit diagrams EPLAN macro files Manuals characteristics operating manuals certificates Product master data You can find mySupport CAx data on the Internet http support industry siemens com my ww en CAxOnline Application example...

Страница 8: ...ew of the module Figure 2 1 View of the IM 157 1 PN interface module Properties The module has the following technical properties Connects the ET 200AL distributed I O system with PROFINET IO 24 V DC supply voltage Support for 2 ET Connection lines Dimensions 45 x 159 mm The functions supported by the module are found in the chapter Functions Page 11 ...

Страница 9: ...he maximum amount of I O data including user data qualifier is limited to 360 bytes per controller Accessories The following component is included with the module in the packaging Identification labels Other components The following component can be ordered as spare part Identification labels The following components can be ordered as accessories Connectors Cables Stripping Tool for PROFINET Strip...

Страница 10: ...T LED displays for the current operating status and diagnostics status X1 P1 R 1st PROFINET interface X1 P2 R 2nd PROFINET interface ET CON1 ET CON2 LED displays for ET Connection X80 Connector for infeed of the supply voltage POWER input X81 Socket for loop through of the supply voltage POWER output X30 Socket for ET Connection1 X31 Socket for ET Connection2 P1 LINK P2 LINK LED displays for the c...

Страница 11: ... SNMP MIB 2 LLDP Port diagnostics Deactivating of ports Real time communication Isochronous real time communication Minimum update time 250 μs Media redundancy MRP Media redundancy with planned duplication MRPD Device replacement with topological configuration Device replacement without topological configuration Shared Device Identification data I M0 to I M4 Firmware update via PROFINET IO Reset t...

Страница 12: ... Systems of third party manufacturers Depending on the range of functions of the third party sys tem Real time communication A transmission method for PROFINET IO based on a cyclic data exchange with a provider consumer model Isochronous real time communication Synchronized transmission method for cyclic exchange of IRT data between PROFINET devices A reserved bandwidth within the send clock is av...

Страница 13: ... Thus allowing flexible automation concepts You have for example the possibility of combining I O modules lying near other into an IO device When operating as a shared device there might be temporary delays in the update of the IO data when establishing or terminating additional communications relationships to an IO controller You can find additional information in the STEP 7 online help and the m...

Страница 14: ...ds in the user program of the PROFINET IO controller Additional hardware is not needed The PROFIenergy commands are interpreted by the PROFINET devices The device which provides PROFIenergy and supports the matching control data record owns the PE Entity the access point for these control data records This PE Entity represents I O modules which do not have their own PE Entity on the interface modu...

Страница 15: ...w 19292127 PROFINET with STEP 7 V14 https support industry siemens com cs ww en view 49948856 function manual section Saving energy with PROFIenergy Application guide for implementation of shutdown concepts with PROFIenergy https support industry siemens com cs ww en view 96837137 Saving energy with SIMATIC S7 STEP 7 as of V5 5 https support industry siemens com cs ww en view 41986454 Saving energ...

Страница 16: ...e and End_Pause Always observe this sequence during programming LED displays PROFIenergy generally has no effect on the LED display Exceptions can be found in the device manuals of the I O modules Response to error detection All channels whose pause mode is set to PE_MODE_PROCEED report errors as in productive operation The following rules apply to channels which switch to a pause mode other than ...

Страница 17: ...ctivated by re sending the PROFIenergy parameter assignment followed by the Start_Pause command Stop controller1 Controller failure connection interrupted 1 Firmware update Reset to factory settings Deactivating the IO device1 The I O module was pulled and plugged Station stop1 Removing an I O module The pause is exited the PROFIenergy parameter assignment is still on the I O module and the pause ...

Страница 18: ...ution of the parameters to the I O modules and returns the result as a return value of the write job In the case of a negative return value there are one or more I O modules that have not accepted the parameter data record In this case the I O modules respond according to their last PROFIenergy parameter assignment in case of an incoming Start_Pause command Start_Pause End_Pause commands can be ex...

Страница 19: ...asured value is retained 4D PE_MODE_SUBST_VALUE substitute value 0 2 64 Block 32 Slot num ber See Block 1 65 Mode 1 The specific behavior depends on the used I O module with a digital input module for example the sensor supply is turned off or the outputs are without power supply and voltage supply with an analog output module 2 An analog output module e g with the output range 0 mA to 20 mA 20 mA...

Страница 20: ...ing the PROFIenergy status PE_Identify 05H Reading the supported PROFIenergy services 1 The minimum configurable pause time for the ET 200AL distributed I O system is 10 s 2 3 3 Configuration control option handling Properties Configuration control allows you to prepare your distributed I O system for future extensions or options Configuration control means that you can configure the planned maxim...

Страница 21: ...ection interface 2L Load voltage 2L switched Internal supply voltage 2M Ground 2M switched X1 P1 R 1 PROFINET interface RUN LED operating state green X1 P2 R 2 PROFINET interface ERROR LED diagnostics status red X80 Infeed of supply voltages MAINT LED diagnostics status yellow X81 Loop through of supply voltages P1 LINK P2 LINK PROFINET LEDs green X30 Infeed of the ET Connection ET CON1 ET CON2 ET...

Страница 22: ...ed cables Pin assignment of the sockets for PROFINET The following table shows the pin assignment of the two sockets for PROFINET Table 3 1 Pin assignment of the PROFINET sockets Pin Assignment Front view of the sockets X1 P1 R Socket X1 P2 R Socket X1 P1 R X1 P2 R 1 TXP RXP 2 RXP TXP 3 TXN RXN 4 RXN TXN Shield ing Functional earth FE Note Pin assignments If you disable Autonegotiation in STEP 7 y...

Страница 23: ...llowing table shows the pin assignment for infeed of the supply voltage Table 3 3 Pin assignment of the supply voltage connector Pin Assignment Assignment of the wire color of the power line cable Front view of the connector X80 connector power input 1 Supply voltage 1L non switched Brown 2 Ground 2M switched White 3 Ground 1M non switched Blue 4 Load voltage 2L switched Black Pin assignment of th...

Страница 24: ...he correct wiring of the M8 sockets for ET Connection and the supply voltage Mixing up the ET Connection connectors and the connectors for the supply voltage can destroy the module CAUTION PROFINET IO Modules with PROFINET interfaces may only be operated under the following condition All connected devices must be equipped with SELV PELV power supplies ...

Страница 25: ...able ET 200AL 4 2 Explanation of the parameters Configuration control You can use this parameter to enable the configuration control function in the ET 200AL distributed I O system Note If you configure the enable the ET 200AL distributed I O system requires a control data record 196 from the user program in order for the ET 200AL distributed I O system to operate the I O modules Reference You wil...

Страница 26: ... messages diagnostics and system alarms 5 5 1 Status and error displays LED displays The figure below shows the LED displays status and error displays of the interface module IM 157 1 PN RUN green ERROR red MAINT yellow ET CON1 green ET CON2 green P2 LINK green P1 LINK green Figure 5 1 LED displays ...

Страница 27: ...uration software ET 200AL starts up ET 200AL is being assigned parameters On Not rele vant Not rele vant ET 200AL is currently exchanging data with the IO controller Not rele vant Flashes Not rele vant Group error Evaluate the diagnostics and eliminate the error The preset configuration does not corre spond to the actual configuration of the ET 200AL Check the configuration of the ET 200AL to see ...

Страница 28: ...ch or IO controller is disconnected On There is no connection between the PROFINET interface of your PROFINET device and a communication partner e g IO controller Flashes The Node flash test is run the RUN ERROR and MAINT LEDs also flash LED ET CON1 LED ET CON2 Table 5 3 Status displays of the LEDs ET CON1 and ET CON2 LEDs Meaning Solution ET CON1 ET CON2 Off There are no I O modules available at ...

Страница 29: ...in the error OB using the instruction RALRM read additional interrupt information System diagnostics In STEP 7 TIA Portal the updated system diagnostic is available for the modules of the S7 1500 automation system IO controller CPU S7 1500 and ET 200AL IO device Independent of the cyclic user program messages are made available on the display of the CPU S7 1500 the CPU web server and the HMI devic...

Страница 30: ...e module interrupt occurs the CPU interrupts execution of the user program and processes the insert remove module interrupt OB OB 83 The event that triggered the interrupt is entered in the start information of the insert remove OB The pull plug OB OB 83 is also triggered for all subsequent I O modules because the ET Connection and or the power supply is interrupted 5 3 Alarms 5 3 1 Diagnostics al...

Страница 31: ...t automation siemens com WW view en 19292127 RDREC instruction SFB 52 Reading data records from the IO device RALRM instruction SFB 54 Receiving alarms from the IO device Additional information on the data records for PROFINET IO The structure of the diagnostics data records and programming examples can be found in the Programming Manual From PROFIBUS DP to PROFINET IO http support automation siem...

Страница 32: ...d in the start information of the OB 82 The interface module signals a maintenance event to the higher level diagnostics system in the case of the following event Table 5 5 Triggering of a maintenance event Maintenance alarm Event Alarm Meaning Maintenance demand ed LED MAINT is lit Synchronization loss No synchronization frame received No synchronization message frame was received by the sync mas...

Страница 33: ...ords is differentiated by the BlockVersion The following BlockVersion applies to the IM 157 1 PN interface modules Table 5 6 Structure of the manufacturer specific diagnostics data records IM 157 1 PN interface module BlockVersion 6ES7157 1AB00 0AB0 W 16 0101 5 3 4 Invalid configuration states of ET 200AL on the PROFINET IO Invalid configuration states If the number of modules exceeds the maximum ...

Страница 34: ...on V5 5 SP4 Hotfix 3 or higher PROFINET as of GSD version GSD revision GSDML V2 3 1 Configuration control Via data record Yes Supply voltage Load voltage 1L Rated value DC 24 V Low limit of permitted range DC 20 4 V High limit of permitted range DC 28 8 V Reverse polarity protection Yes against destruction Input current Current consumption rated value 100 mA From load voltage 1L unswitched current...

Страница 35: ...ces Open IE communication Yes IRT Yes 250 µs 500 µs 1 ms 2 ms 4 ms 8 ms 16 ms 32 ms 64 ms 128 ms MRP Yes MRPD Yes PROFIenergy Yes Shared Device Yes Number of IO controllers with shared device max 4 Open IE communication TCP IP Yes SNMP Yes LLDP Yes Interrupts diagnostics status information Interrupts Yes Diagnostics functions Yes Diagnostics indicator LED RUN LED Yes green LED ERROR LED Yes red LE...

Страница 36: ...f protection and protection class Degree of protection according to EN 60529 IP65 Yes IP67 Yes Ambient conditions Ambient temperature during operation Min 25 C Max 55 C Connection technology Power supply M8 4 pin ET Connection ET Connection M8 4 pin shielded Dimensions Width 45 mm Height 159 mm Depth 40 mm Weights Weight approx 263 g ...

Страница 37: ...M 157 1 PN 6ES7157 1AB00 0AB0 37 Manual 12 2016 A5E32347036 AD Dimension drawing A The figure below shows the dimension drawing of the IM 157 1 PN interface module in the front and side view Figure A 1 Dimension drawing ...

Страница 38: ...at the input data of the I O modules are transmitted via ET Connection without further delay wait time in the interface module via PROFINET The output data from PROFINET is also transmitted without further delay via ET Connection to the I O modules Thus the cycle time of the ET Connection based on then number of I O modules is always a multiple of the configured PROFINET send clock The chart shown...