Installation
7.1 Connecting the SITOP UPS1600 at its input
SITOP UPS1600 / BAT1600 / UPS1100
212
Equipment Manual, 07.2021, A5E37775406-11-76
7.1
Connecting the SITOP UPS1600 at its input
The SITOP UPS1600 is designed to be connected to a 24 V DC supply. The 24 V supply voltage
must comply with SELV (ES1) in accordance with EN62368-1 and EN50178.
Figure 7-1
Input side connection
The 24 V power supply is connected at the "IN+", and "IN-"
①
terminals (see Figure 7-1 Input
side connection (Page 212)).
The cables used must be suitable for temperatures of at least 90 °C.
7.2
Connecting the SITOP UPS1600 at its output
The output of the SITOP UPS1600 is no-load, overload and short-circuit proof. If an overload
occurs, the electronic current limiting function limits the output current to a maximum value
(see Section Technical data (Page 235)).
Figure 7-2
Output-side connection
The output voltage is connected at the "OUT+" and "OUT–"
②
terminals (see Figure Output-
side connection (Page 212)). Ensure that the output cables are dimensioned correctly for the
maximum output current rms value and fused accordingly.
The deployed cables must be suitable for temperatures of at least 90° C.
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...