Parameters
6
6.1
Parameter types
Definition
You can define the mode of operation of the I/O module via the parameter types, thereby
influencing the functions supported by the module.
The time stamp is configured in the configuration dialog of the I/O module.
Description
There are two types of parameters:
• Module/channel parameters (data record 128)
• System parameters (potential group, IO redundancy)
6.2
Module/channel parameters
Definition
Module/channel parameters are specific parameters whose configuration can affect the entire
module or channels.
Description
The following module/channel parameters are available:
Parameters
Value range
Default
Changing parame‐
ter settings in RUN
Efficiency range
Diagnostics, Missing sup‐
ply voltage L+ (Page 21)
• Enabled
• Disabled
Enabled
Yes
Module
IO redundancy
(Page 21)
• None
• 2 modules
None
Yes
Module
Diagnostics: short-cir‐
cuit (Page 21)
• Enabled
• Disabled
Enabled
Yes
Channel
Diagnostics: wire break
(Page 22)
• Enabled
• Disabled
Enabled
Yes
Channel
Diagnostics: change-
over contact error
(Page 22)
• Enabled
• Disabled
Disabled
Yes
Channel
DI 16xNAMUR HA
Equipment Manual, 08/2019, A5E39293880-AD
19
Содержание 6DL1131-6TH00-0PH1
Страница 6: ...Security information DI 16xNAMUR HA 6 Equipment Manual 08 2019 A5E39293880 AD ...
Страница 8: ...Preface DI 16xNAMUR HA 8 Equipment Manual 08 2019 A5E39293880 AD ...
Страница 10: ...2D Matrix code QR code EAN code DI 16xNAMUR HA 10 Equipment Manual 08 2019 A5E39293880 AD ...
Страница 14: ...Product overview 4 3 Terminal blocks DI 16xNAMUR HA 14 Equipment Manual 08 2019 A5E39293880 AD ...
Страница 30: ...Parameters 6 5 Flutter monitoring DI 16xNAMUR HA 30 Equipment Manual 08 2019 A5E39293880 AD ...