Siemens 563-004 Скачать руководство пользователя страница 3

Document No. 563-002

Installation Instructions

January 12, 2007

24 V-AC

C

E

H

C H

DO 1 DO 2 DO 3 DO 4 DO 5

NO C NO C NO C NO C NO C

DO 6 DI  3

DI  2

FLN

TRUNK

NO C AI  3

TX RX

+

-

S

BST

RTS

1   2   3   4   5   6   7   8   9  10 11 12 13 14 15 16

1   2   3   4   5   6   7   8   9  10 11 12 13 14 15 16

WLAN0004R2

TEC Power

(From Transformer)

TEC

(Typical)

Channel

Network I.D.

24 Vac 1.2 VA

24 Vac

Power Line

Alternate

Power

3M Scotchlok

TM

Power Connectors (Typical of 2)

1. Thread TEC power

wire through
connector.

2. Fold up flap to

lock TEC wire
into connector.

3. Insert power wire

from FLNX into
connector so it
appears in window.

4. Use lineman’s

pliers to pinch
connecting bar in 
place and connect
wires internally.

5. Close connector

cover to secure
wires.

TEC

Power Wire

FLNX

Power Wire

Figure 4.

FLNX Communication and Power Wiring.

6. Connect the antenna.

Be sure the antenna is

securely connected to the FLX.

For a remote mount antenna, do the following:

a. Locate the liquid tight

fi

tting so that the

antenna extension cable does not incur
excessive pull force. At the desired enclosure
location, punch a 1/2” knockout and use the
locknut to secure the body of the liquid tight

fi

tting into the knockout.

b. Route the antenna through the body of the

liquid tight

fi

tting (Figure 5). Hand-tighten the

liquid tight

fi

tting nut to secure the antenna in

place.

Make certain the liquid tight

fi

tting nut

tightens on the antenna base, not the
antenna itself, so the antenna can be
articulated.

c. Connect the antenna wire securely to the

FLNX.

Siemens Building Technologies, Inc.

Page 3 of 4

Содержание 563-004

Страница 1: ... Antennas must be ordered separately Accessories 563 027 Pre terminated Cable Kit Includes two 14 cables power and communication Recommended for factory mounting Warning Caution Notations WARNING Personal injury loss of life may occur if you do not follow the procedures as specified CAUTION Equipment damage or loss of data may occur if you do not follow the procedures as specified Expected Install...

Страница 2: ... antenna is brought through a 1 2 knockout Figure 3 The antenna extension cable is 12 long WLAN0016R1 Figure 3 FLNX Mounted Inside Enclosure Installation 1 Determine the optimal location of the FLNX and antenna for RF communications Ideally the antenna should extend below the VAV box 2 Mount the FLNX using the provided screws You can also use double sided tape or VELCRO fasteners 3 Set the Channel...

Страница 3: ...ternally 5 Close connector cover to secure wires TEC Power Wire FLNX Power Wire Figure 4 FLNX Communication and Power Wiring 6 Connect the antenna Be sure the antenna is securely connected to the FLX For a remote mount antenna do the following a Locate the liquid tight fitting so that the antenna extension cable does not incur excessive pull force At the desired enclosure location punch a 1 2 knoc...

Страница 4: ...structions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one of the following measures Reorient...

Отзывы: