Document No. 546-00310 
Installations Instructions  
November 15, 2006 

Page 4 of 6

 

Siemens Building Technologies, Inc. 

3.  Insert the plastic sidewall adapter (provided) 

through the hole from the inside of the hood wall 
and lock it in place from the outside with the 
plastic lock ring (provided). See Figure 5. 

4.  Using a screwdriver and the two-position 

removable wire connector (provided), connect 
the power wires to the removable wire connector 
as shown in Figure 7. 

(Steps 5 and 6 are optional) 

 

5. 

If using a field panel:

 Use the wire strippers, 

and remove 1/4- inch (6.35 mm) of insulation 
from the ends of the FLN trunk wires. 

 

Using a screwdriver, terminate the wires from 
the field panel to the three-position removable 
wire connector. See Figure 7. 

Figure 5.  Installing the Plastic Sidewall Adapter  

and Plastic Lock Ring. 

 

4.  Cut the air sensor hose (provided) to fit between 

the sidewall adapter and the FHM. Leave 
enough slack so that when the hose is installed, 
no kinks are created. 

5.  Carefully insert one end of the air sensor hose 

onto the end of the plastic sidewall adapter and 
insert the other end through the hole in the 
mounting plate. 

Hose and Wire Connections:  

1.  Insert the end of the air sensor hose onto the air 

sensor connection on the back of the FHM. See 
Figure 6. 

 

Figure 7.  Location of Wire Receptacles. 

6. 

If using the auxiliary DI(s) or an external 
alarm:

 Use the wire strippers, and remove  

1/4-inch (6.35 mm) of insulation from the ends of 
the auxiliary or external alarm wires. 

 

Using a screwdriver, terminate the wires from 
the DI or external alarm to the four-position 
removable wire connector. See Figure 7. 

7.  Securely insert all wire connectors into their 

appropriate receptacles. Leave all unused wire 
connectors in their mounting receptacles. 

8.  Place the FHM onto the mounting bracket, being 

careful not to kink the air sensor hose or wires. 

Figure 6.  Wiring and Hose Connections. 

9.  To secure the FHM to the fume hood, tighten the 

screws at the top and bottom tabs of the 
mounting plate. 

2.  Insert all wires that will be terminated to the 

FHM through the hole in the mounting plate. 

3.  Using the wire strippers, remove 1/4-inch  

(0.5 cm) of insulation from the ends of the power 
wires. 

The installation is now complete. 

Содержание 546-00303A

Страница 1: ...l flat blade screwdriver Small Philips screwdriver Wire strippers For a fume hood without an existing cutout Medium duty electric drill 1 8 inch 3 0 mm drill bit 1 2 inch 13 0 mm drill bit Metal cutting saw or 3 4 in and 1 in drill bits or hole saws Small flat blade screwdriver Small Philips screwdriver Wire strippers Expected Installation Time 27 minutes Prerequisites Power cable in place If usin...

Страница 2: ... Existing Cutout Mounting Plate Installation with an Existing Cutout 1 See Figure 3 If the fume hood is provided with a 2 inch 4 inch 5 0 10 0 cm cutout with an electric utility box then use the provided machine screws to attach the mounting plate to the electric utility and skip to Sidewall Hole Mounting If the fume hood has no electric utility box make sure that the cutout provides enough cleara...

Страница 3: ...n without an Existing Cutout 3 Using a metal cutting saw or other suitable tool remove the marked rectangular area 4 Using a 1 8 inch 3 0 mm bit drill the two mounting holes 5 Using the screws provided attach the mounting plate to the mounting surface 6 Proceed to Sidewall Hose Mounting Sidewall Hose Mounting NOTE The location of the sidewall adapter greatly affects the performance of the Fume Hoo...

Страница 4: ...r sensor hose onto the end of the plastic sidewall adapter and insert the other end through the hole in the mounting plate Hose and Wire Connections 1 Insert the end of the air sensor hose onto the air sensor connection on the back of the FHM See Figure 6 Figure 7 Location of Wire Receptacles 6 If using the auxiliary DI s or an external alarm Use the wire strippers and remove 1 4 inch 6 35 mm of i...

Страница 5: ...Document No 546 00310 Installations Instructions November 15 2006 Siemens Building Technologies Inc Page 5 of 6 Figure 8 Full Size Template Location of Holes for Using a Drill ...

Страница 6: ...to make changes in specifications and models as design improvements are introduced 2000 Siemens Building Technologies Inc Siemens Building Technologies Inc Landis Staefa Division 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 U S A Document No 546 00310 Printed in the U S A Page 6 of 6 Figure 9 Full Size Template Location of Hole for Using a Metal Cutting Saw ...

Отзывы: