Document No. 538-588 
Installation Instructions 
Rev. 3, December, 2001 

Page 2 of 3 

Siemens Building Technologies, Inc. 

Prerequisites 

 

CAUTION:   

Avoid mounting the hub in a position that 
forces the fiber to make turns tighter than a 
three-inch radius. The mounting surface 
must also be vibration free. 
 

• 

Fiber cables installed and terminated with 
the proper connectors. 

• 

Individual fibers identified as Transmit and 
Receive. 

• 

A report from the installer showing the loss 
of optic power per section of fiber cable, 
including all connectors. The loss must be 
less than the required link budget. 

• 

Source of transient protected for 115 Vac or 
230 Vac. All Field Panel outlets are 
protected or an MOV protected 120 Vac 
duplex outlet (529-804), or three 250V 
MOVs (527-969) connected for 230V 
operation (refer to Figure 6) can be ordered. 

• 

The BLN or FLN trunk has been checked for 
opens, shorts, and proper shielding. 

• 

The mounting bracket (if used), or other 
locally fabricated bracket, is available. 

 

Instructions 

 
1. 

If wall or rack mounting brackets are being 
used, refer to the installation instructions for the 
brackets (P/N 538-718). 

2. 

Remove the protective cap from the transmit 
port and transmit fiber, and connect the fiber to 
the port labeled “TX1” (refer to Figure 2). Do not 
use any tools to tighten the connectors. 

3. 

Remove the protective cap from the receive 
port and receive fiber, and connect the fiber to 
the port labeled “RX1” (refer to Figure 2). Do 
not use any tools to tighten the connectors. 

4. 

Repeat Steps 2 and 3 for the remaining ports. 
Remember to keep the transmit and receive 
fibers together on the same numbered TX and 
RX ports for a remote interface. 

5. 

Connect the DC power cord of the power pack 
and plug the power pack into the transient 
protected for 115 Vac or 230 Vac source. 

 

 

6. 

If multiple hubs are to be configured on the 
same logical trunk, then repeat Steps 1 through 
5 for as many trunks as required. Then use the 
hub inter-connect cables to connect the hubs 
together into one logical network. 

When connecting an inter-hub trunk to an older 
style hub (the older style uses two RJ11 
connectors) use the following pin connections: 
on the OUT port pin 3 is “+” and pin 4 is “-“; on 
the IN port pin 4 is “+” and pin 3 is “-.“ Use a 
locally obtained RJ11 cable with one end cut to 
connect the OUT or IN port of the older hub to 
the new style hub. 
 
Use trunk terminators at each end of the trunk 
when either more than two hubs are connected 
via the inter-hub trunk, or the inter-hub trunk 
connects to a local trunk. 
 

7. 

Connect the earth ground wire (2’ green wire, 
included) from the trunk shield connection to 
earth ground. The ground can be either the field 
panel chassis using the nutdriver to put the 
ground terminal under the chassis mounting 
nut, or the electrical box which powers the 
interface. 

The installation is now complete. 

 

 

NT0214R1

BRACKET

FACE

BRACKET

INTERFACE

MOUNTING

SCREW

INTERFACE

BACK 

END BEZEL

 

Figure 3.  Rack Mount of Fiber Optic Hub (Side View). 

 
 
 
 

 

 

 

 
 