Overload Relay with Phase-Failure Sensitivity 

3UA50

3UA52 

GB14048.4

DIN VDE0660

Part 102

IEC 60947-4-1

 

Q/SMS 001

XK06-201 0023

 

Instructions 

Order No.

 4NEB 601 1482-30 *5 

English 

A001253 

 

    

!

    

Limited protection against contact with live parts.

 

Degree of protection IP 20 to IEC 60529. 
Safe from finger touch to DIN VDE 0106,Part 100. 

Commissioning and maintenance by qualified personnel only. 
Follow the operating Instructions! 

 

 

                     WARNING 

 

Hazardous voltage can cause electrical 

shock and burns. 

Disconnect power before proceeding with 

any work on this equipment. 

Fig. I

  3UA50: For mounting on contactors 3TD40/41, 3TE40, 3TF30/31/40/41, 

3TW10/12/40/41; 
Individual mounting possible with assembly kit 3UX14 18. 

3UA52:  For mounting on contactors 3TD42/43, 3TE42, 3TF32/33/42/43, 

3TW13/42/43; 

Individual mounting possible with assembly kit 3UX14 20. 

 

Installation 

Dimension drawings

 (dimensions in mm):

 Fig. II

 

a    3UA50: for individual mounting with assembly kit 3UX14 18 

3UA52: for individual mounting with assembly kit 3UX14 20 

b    3UA50: for mounting on contactor 3TF30/31 
c    3UA50: for mounting on contactor 3TF40/41 

I=contactor with 1 NO or 1 NC 
II=contactor with 1NO + 1NC or 2NO + 2NC 

d   3UA52: for mounting in contactor 3TF32/33 
e   3UA52: for mounting in contactor 3TF42/43 

1) 

  Minimum distance from earthed components 

2) 

  For snap-on mounting on a standard sectional rail to DIN EN 50022.  

3)  

 Dimension for square OFF button (stoke 3mm). 

4)

  Dimension for round RESET button (stroke 2.5mm) dimension minus 2.5mm. 

 

Permissible installed positions: 

Fig. III 

a   Overload relay with contactor 
b   Overload relay for individual mounting  
Do not subject to sudden shocks or long-term vibrations. 
Mounting: 
Snap-on mounting on a standard sectional rail (35mm) to EN 50 022 or bolting on a plane 
surface by two bolts to be secured by washers and spring washers. 
 

Connection 

Equipment circuit diagram: 

  

Fig. IV

 

Permissible cable cross-sections:  Fig. V 

In the case of several single-phase loads, the three main circuits must be connected in series. 
 

Commissioning

 

Instructions:   Fig. 

VI

 

  Set the scale to the rated current of load. 

② 

Reset button (blue) 
Push this button before commissioning and after tripping to make relay ready for 
operation. 
In the as-delivered condition, the auxiliary contact is set to H=Manual resetting. 
To change from H=Manual to A=Automatic, press and turn the button counter-
clockwise from H to A. 

③ 

Test button (red)  
When this button is actuated, the NC contact opens and the NO contact closes, i.e. 
a test function for NC and NO contacts (simulation of overload tripping). 
In the “Manual” position, the relay is reset when the blue button is pressed. 
In the “Automatic” position, the relay is reset automatically when the red button is 
released. 

④ 

TRIPPED indication (green) 
In the H setting, a green pin protrudes from the front plate to indicate the TRIPPED 
condition. In the A setting, this condition is not indicated. 

 Terminal for contactor coil, A2. 

Tripping characteristics: 

 

Fig. VII

 

The characteristics conform to VDE0165, VDE 0170/0171 for machines with type of 
protection E Ex e. 
Tripping times are shown for a three-phase load from the cold state (ambient temperature 
+20 

). In the case of hot relays, preloaded with 1

×

I

E

, the tripping times decrease by 

approx. 25%. 
I

     Current setting  

t

A

     Tripping time in seconds (

±

20% ) 

① 

  Setting range 

        (I= lowest value of current setting I

E,  

II= highest value of current setting I

E

 ) 

   Type designation/Order No. 

   PTB (Federal testing Laboratories) Test Report No. 

 

Technical data  

Main circuit  

Rated insulation voltage   

690V 

Rated operational current   

3UA50: 0.1~14.5 A 

   3UA52: 

0.1~25 

Permissible ambient air temperature  -25 

 to +55 

 

Short-circuit protection  

see 

nameplate 

 

Auxiliary circuit  

Rated operational currents 

AC-15/Ue  V  24  60  125  230  400 500 690 
AC-15/Ie A 2  1.5 1.25 

1.15 

1.1 

1 0.8 

DC-13/Ue 

24 

60 

110 

220 

   

DC-13/Ie  A 2  0.5 0.3 0.2      

 

Rated insulation voltage: 
 
400V 

  690V 

differing potential 

 same 

potential 

 

Short-circuit protection:  
NH, NEOZED or DIAZED fuses 

6A gG or 10A, fast 

Miniature circuit-breaker   3A 

(C-characteristic) 

 

Operating conditions at ambient temperatures>55 

 

At ambient temperatures > 55 

you must

 

 

1. Reduce the current loading for the overload relay 
2. Upwardly correct the setting current to prevent tripping at motor rated current. 
Correction factors: 

Ambient 

temperature 

Perm. current loading referred 

to end-of-scale value 

Setting current 

correction 

55

 1  1 

60

 0.94  1.08 

65

 0.88  1.09 

70

 0.82  1.1 

 

Calculation example: 
Motor rated current: 

10 A 

Ambient temperature: 

70 

 

Overload relay fitted: 

8~12.5 A 

 

1st Step: Determine the permissible current loading: 
Max. Current loading: 12.5 A 

×

 0.82 =10.25 A 

Loading with motor rated current 10 A at 70 

 

ambient temperature is permissible. 

 

2nd Step: Calculate the setting current: 
Motor rated current: 10 A 
Setting current correction: 10 A 

×

 1.1=11 A 

You must set the overload relay to 11 A.  

 

For further information and accessories, see Catalog.

 

 

 

Siemens Electrical Apparatus Ltd., Suzhou

2

Содержание 3UA50

Страница 1: ... 复位按钮 蓝色 在投入运行前和脱扣后 按一下本按钮使继电器处于待工 作状态 出厂时本按钮被置于 H 即手动复位状态 若需转换到 A 即自动复位状态 按下本按钮并逆时针方向从H转到 A即可 试验按钮 红色 当按下本按钮后 动断触头打开 动合触头闭合 即动 断 动合触头的试验功能 模拟过载脱扣 在手动复位状态 再按下蓝色按钮时继电器复位 在自动复位状态 当放开本按钮时继电器即复位 脱扣指示件 绿色 在手动复位状态 当继电器脱扣时本指示件将从面罩上伸 出 表示继电器已脱扣 在自动复位状态则无此显示 接触器线圈接线端子 A2 脱扣特性曲线见图 VII 这些特性曲线符合VDE0165 VDE0170 0171 适用于增安 型电机 图所示为三相负载从冷态 环境温度 20 C 开始的 脱扣时间 若继电器以1 IE 电流预热 脱扣时间将减少大约 25 IE 整定电流 tA 脱扣时间 单位 秒 20 整定...

Страница 2: ...e from H to A Test button red When this button is actuated the NC contact opens and the NO contact closes i e a test function for NC and NO contacts simulation of overload tripping In the Manual position the relay is reset when the blue button is pressed In the Automatic position the relay is reset automatically when the red button is released TRIPPED indication green In the H setting a green pin ...

Страница 3: ...Ⅰ Ⅴ Ⅵ L1 L2 L3 T1 T2 T3 NO NC 1 1 5 Nm 9 13 lb in 0 8 1 4 Nm 7 12 lb in 2 2 5 6 mm2 2 0 5 1 mm2 2 1 2 5 mm2 2 1 5 4 mm2 2 0 5 1 mm2 2 0 75 2 5mm2 AWG 2 15 4 2 18 12 3 ...

Страница 4: ...Ⅶ II 8 资料如有更改 恕不另行通知 地址 苏州新区珠江路455号 电话 0512 66611188 邮政编码 215129 印刷 2002 08 http www ad siemens com cn about_us jv seal asp 4 ...

Отзывы: