Overload Relay with Phase-Failure Sensitivity
3UA50
,
3UA52
GB14048.4
,
DIN VDE0660
,
Part 102
,
IEC 60947-4-1
Q/SMS 001
,
XK06-201 0023
Instructions
Order No.
:
4NEB 601 1482-30 *5
English
A001253
!
Limited protection against contact with live parts.
Degree of protection IP 20 to IEC 60529.
Safe from finger touch to DIN VDE 0106,Part 100.
Commissioning and maintenance by qualified personnel only.
Follow the operating Instructions!
!
WARNING
Hazardous voltage can cause electrical
shock and burns.
Disconnect power before proceeding with
any work on this equipment.
Fig. I
3UA50: For mounting on contactors 3TD40/41, 3TE40, 3TF30/31/40/41,
3TW10/12/40/41;
Individual mounting possible with assembly kit 3UX14 18.
3UA52: For mounting on contactors 3TD42/43, 3TE42, 3TF32/33/42/43,
3TW13/42/43;
Individual mounting possible with assembly kit 3UX14 20.
Installation
Dimension drawings
(dimensions in mm):
Fig. II
a 3UA50: for individual mounting with assembly kit 3UX14 18
3UA52: for individual mounting with assembly kit 3UX14 20
b 3UA50: for mounting on contactor 3TF30/31
c 3UA50: for mounting on contactor 3TF40/41
I=contactor with 1 NO or 1 NC
II=contactor with 1NO + 1NC or 2NO + 2NC
d 3UA52: for mounting in contactor 3TF32/33
e 3UA52: for mounting in contactor 3TF42/43
1)
Minimum distance from earthed components
2)
For snap-on mounting on a standard sectional rail to DIN EN 50022.
3)
Dimension for square OFF button (stoke 3mm).
4)
Dimension for round RESET button (stroke 2.5mm) dimension minus 2.5mm.
Permissible installed positions:
Fig. III
a Overload relay with contactor
b Overload relay for individual mounting
Do not subject to sudden shocks or long-term vibrations.
Mounting:
Snap-on mounting on a standard sectional rail (35mm) to EN 50 022 or bolting on a plane
surface by two bolts to be secured by washers and spring washers.
Connection
Equipment circuit diagram:
Fig. IV
Permissible cable cross-sections: Fig. V
In the case of several single-phase loads, the three main circuits must be connected in series.
Commissioning
Instructions: Fig.
VI
①
Set the scale to the rated current of load.
②
Reset button (blue)
Push this button before commissioning and after tripping to make relay ready for
operation.
In the as-delivered condition, the auxiliary contact is set to H=Manual resetting.
To change from H=Manual to A=Automatic, press and turn the button counter-
clockwise from H to A.
③
Test button (red)
When this button is actuated, the NC contact opens and the NO contact closes, i.e.
a test function for NC and NO contacts (simulation of overload tripping).
In the “Manual” position, the relay is reset when the blue button is pressed.
In the “Automatic” position, the relay is reset automatically when the red button is
released.
④
TRIPPED indication (green)
In the H setting, a green pin protrudes from the front plate to indicate the TRIPPED
condition. In the A setting, this condition is not indicated.
⑤
Terminal for contactor coil, A2.
Tripping characteristics:
Fig. VII
The characteristics conform to VDE0165, VDE 0170/0171 for machines with type of
protection E Ex e.
Tripping times are shown for a three-phase load from the cold state (ambient temperature
+20
℃
). In the case of hot relays, preloaded with 1
×
I
E
, the tripping times decrease by
approx. 25%.
I
E
Current setting
t
A
Tripping time in seconds (
±
20% )
①
Setting range
(I= lowest value of current setting I
E,
II= highest value of current setting I
E
)
②
Type designation/Order No.
③
PTB (Federal testing Laboratories) Test Report No.
Technical data
Main circuit
Rated insulation voltage
690V
Rated operational current
3UA50: 0.1~14.5 A
3UA52:
0.1~25
A
Permissible ambient air temperature -25
℃
to +55
℃
Short-circuit protection
see
nameplate
Auxiliary circuit
Rated operational currents
AC-15/Ue V 24 60 125 230 400 500 690
AC-15/Ie A 2 1.5 1.25
1.15
1.1
1 0.8
DC-13/Ue
V
24
60
110
220
DC-13/Ie A 2 0.5 0.3 0.2
Rated insulation voltage:
400V
690V
differing potential
same
potential
Short-circuit protection:
NH, NEOZED or DIAZED fuses
6A gG or 10A, fast
Miniature circuit-breaker 3A
(C-characteristic)
Operating conditions at ambient temperatures>55
℃
At ambient temperatures > 55
℃
,
you must
1. Reduce the current loading for the overload relay
2. Upwardly correct the setting current to prevent tripping at motor rated current.
Correction factors:
Ambient
temperature
Perm. current loading referred
to end-of-scale value
Setting current
correction
55
℃
1 1
60
℃
0.94 1.08
65
℃
0.88 1.09
70
℃
0.82 1.1
Calculation example:
Motor rated current:
10 A
Ambient temperature:
70
℃
Overload relay fitted:
8~12.5 A
1st Step: Determine the permissible current loading:
Max. Current loading: 12.5 A
×
0.82 =10.25 A
Loading with motor rated current 10 A at 70
℃
ambient temperature is permissible.
2nd Step: Calculate the setting current:
Motor rated current: 10 A
Setting current correction: 10 A
×
1.1=11 A
You must set the overload relay to 11 A.
For further information and accessories, see Catalog.
Siemens Electrical Apparatus Ltd., Suzhou
2