Maintenance
9229 0106 176 0-
45
2020-09-18
Configuration of supply
voltage
U
a
of the electronic
controller
Using the DIP switches S2 (26) and the set-up matrix, have the customer adjust the
settings on the electronic controller.
Fig. 50
Matrix of the positions of the DIP switches S2 (shown in black) for addi-
tional closing and opening delay
1)
Average values under normal conditions. Deviations possible under different ambient conditions.
2)
If closing latching is available, the opening delay is disabled and DIP switch S2 in positions 3 and
4 is to be left OPEN.
Supply voltage
U
a
Closing delay
Openin
g dela
y 1
Openin
g dela
y 2
Spare
Latch
(Shunt
release
)
Switc
h pos
iti
o
n
Clo
sing delay
Open
ing d
elay
1)
110 V–125 V AC/DC,
220 V–250 V DC,
230 V–240 V AC
24 V–32 V DC and
48 V–60 V DC
1
2
3
4
5
6
ms
ms
ms
ms
OPEN
0
0
0
0
CLOSE
OPEN
0
30
0
50
CLOSE
OPEN
0
60
0
0
CLOSE
OPEN
0
90
0
50
CLOSE
OPEN
50
0
50
0
CLOSE
OPEN
50
30
50
50
CLOSE
OPEN
50
60
50
0
CLOSE
OPEN
50
90
50
50
CLOSE
1
2
3
4
5
6
Supply voltage range
OPEN
48 V–60 V DC,
220 V–250 V DC,
230 V–240 V AC
48 V–60 V DC
CLOSE
OPEN
24 V–32 V DC and
110 V–125 V AC/DC
24 V–32 V DC
CLOSE
1
2
3
4
5
6
Code for closing latching
OPEN
Without closing latching
CLOSE
OPEN
With closing latching2)
CLOSE
Содержание 3TM
Страница 12: ...Transport storage packaging 12 9229 0106 176 0 2020 09 18 Blank page ...
Страница 26: ...Description 26 9229 0106 176 0 2020 09 18 Blank page ...
Страница 36: ...Installation 36 9229 0106 176 0 2020 09 18 Blank page ...
Страница 48: ...Maintenance 48 9229 0106 176 0 2020 09 18 Blank page ...
Страница 50: ...Index 50 9229 0106 176 0 2020 09 18 Blank page ...