![Siemens 3TK2845 Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/siemens/3tk2845/3tk2845_manual_383059015.webp)
Functional Information
3TK2845 Multifunction Device Manual
GWA 4NEB 926 2087-22 DS 01
2-3
mats establish a cross-circuit between the two input channels of the evaluation
system when stepped on. This means that
1. in the case of a sensor which interrupts the sensor circuit, a cross-circuit
leads to a fault.
2. in the case of safety mats an interruption of the sensor circuit leads to a
fault.
All safety mats and switching strips with 4-conductor-technology functioning
according to the cross-circuit tripping principle can be connected to the 3TK2845
safety relays.
The tripping of the 3TK2845 is initiated by a cross-circuit in the sensor cables.
A safe evaluation according to DIN EN 1760-1 and DIN EN 1760-2 is possible
with a safety mat resistance of < 1000
Ω
for the safety mat + connecting cables.
The 3TK2845 automatically recognizes the mode of operation of the connected
sensor.
If, during first activation of the sensor after a device restart,
1. an opening of the sensor circuits is detected, the 3TK2845 only accepts
sensors which open the sensor circuits (floating NC contacts such as
EMERGENCY-STOP control switches or position switches). A cross-circuit
between the sensor circuits leads to a fault.
2. a cross-circuit is detected between the sensor circuits, the 3TK2845 only
accepts sensors causing a sensor circuit short-circuit (safety mats). An
opening of the sensor circuits leads to a fault.
Содержание 3TK2845
Страница 6: ...3TK2845 Multifunction Device Manual iv GWA 4NEB 926 2087 22 DS 01 ...
Страница 38: ...Functional Information 3TK2845 Multifunction Device Manual 2 26 GWA 4NEB 926 2087 22 DS 01 ...
Страница 44: ...Technical Data 3TK2845 Multifunction Device Manual 3 6 GWA 4NEB 926 2087 22 DS 01 ...
Страница 66: ...3TK2845 Multifunction Device Manual 5 16 GWA 4NEB 926 2087 22 DS 01 ...
Страница 68: ...3TK2845 Multifunction Device Manual GWA 4NEB 926 2087 22 DS 01 ...