Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092

E87010-A0519-T003-A7-3RE4 

Instructions
Installation
Operation
Maintenance
Replacement

March, 2019

A5E46948882A-002     

3RE4

Non-Combination Motor

Controllers

For replacement parts information or an application guide, 

visit our  website at www.usa.siemens.com/controls, 

or contact your local Siemens sales office.

s

IMPORTANT 

These instructions do not purport to cover all details or variations in equipment, nor to 

provide for every possible contingency to be met in connection with installation, 

operation or maintenance, should further information be desired, or should particular 

problems arise which are not covered sufficiently for the purchaser’s purposes, the 

matter should be referred to the local Siemens sales office. The content of this 

instruction manual shall not become part of or modify any prior or existing agreement, 

commitment or relationship. The sales contract contains the entire obligation of 

Siemens. The warranty contained in the contract between the parties is the sole 

warranty of Siemens. Any statements contained herein do not create new warranties 

or modify the existing warranty. 

Hazardous Voltage. 
Will cause death or serious injury. 
Turn off and lock out all power supplying 
this device before working on this device. 
Replace all covers before power 
supplying this device is turned on. 

 

 

DANGER

Description

3RE4 non-combination motor controllers include a 

horsepower rated contactor and an overload relay 

(OLR) with a reset operator (for motor starters). 

They may also include optional factory installed 

accessories such as pilot devices and a control 

power transformer.

The NEMA Type 1 enclosures have a lift-off cover. 

They are suited for general purpose indoor applica-

tions only.

The NEMA Type 3/3R/4/12 enclosures have a 

removable hinged door. They are water and dust 

tight and are suited for outdoor as well as indoor 

applications. 

The NEMA Type 4X 304 stainless steel enclosures 

are noncorrosive and have a removable hinged 

door. They are water and dust tight and are suited 

for outdoor as well as indoor applications.

Pre-Installation

1.   Examine the enclosure and each component for   

      shipping damage. Notify carrier for a claim if any       

      damage is found. DO NOT attempt to install or 

      apply power to any damaged product.

2.   Verify that the horsepower, voltage and current 

      rating of the motor do not exceed the controller 

      rating.

3.   If the control circuit is to be powered by an 

      external source, verify that the supply voltage 

      matches the voltage rating of the contactor coil.

4.   If a control power transformer is supplied with 

      the controller, verify that the supply voltage 

      matches the primary voltage of the control 

      power transformer.

5.   For controllers other than size S2 starters, skip 

      this step and proceed to the next one. Size S2 

      starters are shipped with the OLR uncoupled 

      from the contactor. This is to help prevent 

      damage should the product be mishandled 

      during shipment. The OLR must be coupled to 

      the contactor by following these steps:

 

a.   Couple the OLR to the contactor as   

 

      shown in Figure 1.

 

b.   A jumper wire should already be 

 

      connected to terminal A2 on the contactor. 

 

      Route the loose end of the wire between 

 

      the contactor and OLR as shown in 

 

      Figure 2.

 

c.   Connect the loose end of the wire to 

 

      terminal 95 on the OLR.

1

Содержание 3RE4

Страница 1: ...include optional factory installed accessories such as pilot devices and a control power transformer The NEMA Type 1 enclosures have a lift off cover They are suited for general purpose indoor applica tions only The NEMA Type 3 3R 4 12 enclosures have a removable hinged door They are water and dust tight and are suited for outdoor as well as indoor applications The NEMA Type 4X 304 stainless steel...

Страница 2: ...osures use UL Listed conduit hubs with the same NEMA Type rating as the enclosure Joint compound or equivalent is recommended on conduit threads to prevent water from entering the enclosure 5 Check that all wiring is secure and does not interfere with proper operation of any device 6 Check that all wiring connections including factory connections are proper and tightened to the proper torque value...

Страница 3: ...E87010 A0519 T003 A7 3RE4 Page 3 Siemens Industry Inc 5300 Triangle Parkway Norcross GA 30092 A5E46948882A 002 Figure 2 Typical for both thermal and solid state OLRs Figure 3a Thermal OLR ...

Страница 4: ... torque Screw 7 10 lb in Contactor auxiliary contact solid stranded conductors 2x 20 16 2x 18 14 2x 12 CU 75 C OLR auxiliary contact connection type torque Screw 7 10 lb in OLR auxiliary contact solid stranded conductors Thermal 2x 20 16 2x 18 14 CU 75 C Solid State 1x 20 14 2x 20 14 CU 75 C Wire Type and Connection Torque Specifications Replacement Parts Description Part Number Contactor parts Ob...

Отзывы: