Description
9229 9862 176 0D
23
2013-08-28
Closing solenoid (Y9) 3AY1510
1st shunt release (Y1) 3AY1510
The closing solenoid Y9 unlatches the charged closing
spring and switches the vacuum circuit-breaker on
electrically. It is available for DC or AC voltage.
The closing solenoid Y9 is not designed for continuous
operation and is automatically deactivated within the
circuit-breaker.
The operator's supply voltage may deviate from the
rated supply voltage of the vacuum circuit-breaker by
-15 % to 10 %.
The closing solenoid Y9 can be operated using AC or DC
voltage and is protected against overvoltage.
Power consumption is approximately 140 W / VA
Fig. 26
Closing solenoid (53.1)
In the case of the 1st shunt release Y1, the electrically
fed tripping pulse is passed to the “OPEN” latch by
means of a directly acting magnet armature, thus
switching off the vacuum circuit-breaker.
The 1st shunt release Y1 is not designed for continuous
operation and is automatically deactivated within the
circuit-breaker.
The operator's supply voltage may deviate from the
rated supply voltage of the vacuum circuit-breaker by
-30 % to +10 % in the event of DC voltage and by –15 %
to +10 % in the event of AC voltage.
The 1st shunt release Y1 can be operated using AC or
DC voltage and is protected against overvoltage.
Power consumption is approximately 140 W / VA
Fig. 27
1st shunt release (54.1)
Содержание 3AH4
Страница 4: ...4 9229 9862 176 0D 2013 08 28 Blank page ...
Страница 14: ...Transport storage and packing 14 9229 9862 176 0D 2013 08 28 Blank page ...
Страница 42: ...Description 42 9229 9862 176 0D 2013 08 28 Blank page ...
Страница 52: ...Operation 52 9229 9862 176 0D 2013 08 28 Blank page ...
Страница 60: ...Maintenance 60 9229 9862 176 0D 2013 08 28 Blank page ...
Страница 62: ...Index of keywords 62 9229 9862 176 0D 2013 08 28 Blank page ...