Appendix
48 VDC
125 VDC
250 VDC
120 VAC
240 VAC
1. Current at nominal voltage. 2. Capacitor trip.
Table A-2
Type 3AH Circuit Breaker Ratings
Seconds
Control Voltages, ANSI C37.06
Spring Charging Motor
Nominal
Range
Close Coil
Trip Coil
Amperes
Charging
Close
Trip
Amperes
(1)
Amperes
(1)
Run (Avg.)
(1)
10
10
10
10
10
8
4
2
6
3
2.0
5.4
2.1
—
(2)
—
(2)
2.1
1.0
0.5
0.9
0.4
28-56
70-140
140-280
104-127
208-254
36-56
100-140
220-280
104-127
208-254
Table A-3
Interrupting Capacity of Breaker Auxiliary Switch Contacts
Continuous Current
Amperes
Control Circuit Voltage
Interrupting Capacity in Amperes
Non-Inductive
Inductive
20
20
10
10
5
5
20
(1)
5
5
3
3
120 VAC
240 VAC
48 VDC
125 VDC
250 VDC
Type of Circuit
to Interrupt
20
(1)
1. 2 Contacts in series.
Table A-4
Circuit Breaker Weights
Weights, approx. Lbs (approx. kg)
(1)
Breaker Type
Continuous Current, Amperes
1200 A
2000 A
3000 A
Interrupting Capability
kA rms sym. (MVA)
Maximum Voltage
kV rms sym.
1. For shipping, add 100 lbs (45 kg).
4.76
31.5 (250)
242 (110)
264 (120)
——
4.76
40 (350)
246 (112)
268 (122)
286 (130)
4.76
50
330 (150)
363 (165)
396 (180)
8.25
40 (500)
246 (112)
268 (122)
286 (130)
15.0
20 (500)
165 (75)
257 (117)
——
15.0
25
165 (75)
257 (117)
——
15.0
31.5 (750)
242 (110)
264 (120)
——
15.0
40 (1000)
246 (112)
268 (122)
286 (130)
15.0
50
330 (150)
363 (165)
396 (180)
27.0
25
264 (120)
286 (130)
——
38.0
31.5 (1500)
363 (165)
385 (175)
——
32