Properties
1.1 2AO U HF analog electronic module (6ES7135-4LB02-0AB0)
2AO U HF analog electronic module (6ES7135-4LB02-0AB0)
10
Manual, 04/2007, A5E01076940-01
Suppression of interference, limits of error
Crosstalk between the outputs
Min. -60 dB
Operational limit
± 0,1 %
Intrinsic error limit
± 0,05 %
Temperature error (with reference to the output
range)
±0.003%/K
Linearity error (with reference to the output range) ± 0,01 %
Repeatability (in steady state at 25°C with
reference to output range)
± 0,01 %
Transmitter selection data
Output range (rated value)
±5 V
±10 V
1 V to 5 V
Load impedance (in the rated range of the output)
•
At voltage outputs
Capacitive load
Min. 1.0 kΩ
Max. 0.5 µF
Voltage output
•
Short circuit protection
•
Short circuit voltage
yes
approx. 25 mA
Destruction limit against voltages/currents applied
from outside
•
Voltage at the outputs to M
ANA
Max. 15 V continuous; 75 V for max. 1 ms
(sampling ratio 1:20)
Connection of actuators
•
Voltage output
2-wire connection
4-wire connection
Possible, without compensation of the line
resistances
Possible
I&M functions
The I&M data can be read from the module using interface modules with the following order
numbers or firmware/product versions (or higher):
Interface module
Order number
Firmware version
Product version
IM151-1 HIGH FEATURE
6ES7151-1BA01-0AB0
V2.0
02
IM151-3 PN
6ES7151-3AA20-0AB0
V4.0
01
IM151-3 PN HIGH FEATURE
6ES7151-3AA20-0AB0
V4.0
01
IM151-3 PN FO
6ES7151-3BB21-0AB0
V4.0
01
Note
Using the module after an IM151-7 CPU
If the module is positioned after an IM151-7 CPU, it outputs the last values before a RUN-
STOP transition, provided no values were output by the user program after the STOP-RUN
transition.
Take this into account when programming the control function startup (OB100 or OB1).